Leave sufficient wire tail length to enable the connection to be remade if a mat is to be replaced, but
ensure that the interconnecting wires will fit easily under the edge trim without crushing. Join the wires
using butt connectors supplied as shown in Fig. 24 below. Where mat wires require extending, e.g. front
mat to rear mat connections, and control unit connections, use an extra pair of the butt connectors and a
length of twin wire (see wiring specification - section 6.2).

Fig. 24

UNITING TRIM FIXING
All active uniting trim sections used in installation must be mitred to 45°. This aids in installation and
helps retain overall sensitivity of the sensing area.

Fig. 24a

PERIMETER TRIM FIXING

Where the wiring to the control unit is not buried, notch the perimeter trim at the wire entry and exit
positions and cut the trim slope to suit the conduit system selected. Take care to notch completely so
that any flexing of the perimeter trim will not trap the wiring. Ensure that there are no sharp edges or
burrs which could damage the wires.

Fig. 25 Details of trim fixings

SUGGESTED CUT-OUT
FOR MAT WIRES
ENTERING CABLE
TRUNK (BASE OF
PERIMETER TRIM)

SUGGESTED
CUT-OUT
FOR FLEXIBLE
CONDUIT ENTRY

440F-T3013
Aluminium internal corner
perimeter trim
(Use with 440F-T3510,
440F-T3310 & 440F-T3210)

440F-T3012
Aluminium external corner
perimeter trim
(Use with 440F-T3510,
440F-T3310 & 440F-T3210)

STRAIN RELIEF
CLAMP

FLEXIBLE
CONDUIT

CUT SLOTS HERE

USE EDGE GROMMETS
OVER SHARP EDGES

Strip wires 8mm and
insert into crimp barrel.

Crimp using the correct
cavity size on the crimp
tool.

Heat crimped splice, using
heat gun with deflector,
until tubing shrinks and
adhesive shrinks and flows.

27

440F-T3210, 440F-T3310
& 440F-T3510

440F-T3211 & 440F-T3411

For external corner trim use 440F-T3014. For internal corner trim use 440F-T3015.

440F-T3210, 440F-T3310
& 440F-T3510

Use strain relief clamp with flexible conduit

MAT 1

MAT 2

MAT 1

MAT 2

MAT 3

MAT 1

MAT 2

45

°

45

°

MAT 3

MAT 4

MITRE ALL TRIMS TO 45

°

AS SHOWN IN MAT LAYOUTS