Wiring your surecross® device, Pin euro-style wiring (nodes), Dx80...c wiring – Banner SureCross DX80 Wireless Networks User Manual

Page 4

Advertising
background image

* Default configuration

Debounce establishes how to examine a signal’s transitions. The factory default
setting is to activate the input filtering to compensate for unclean state transi-
tions. To turn off the input filtering, set the switch to the ON position.

Device switches

Counter switches

Inputs. Counter switches 6 and 7 define the inputs as self-energized, sinking
(NPN), or sourcing (PNP). A self-energized input does not require pull-up or
pull-down devices for proper operation. A magnetic pick-up is a self-energized
input. The input threshold can be adjusted to compensate for low amplitude sig-
nals.

Threshold. The counter has a selectable input threshold of 0.25V or 1.5V. For
sinking (NPN) or sourcing (PNP) inputs, set the threshold to 1.5V.

Wiring Your SureCross® Device

Use the following wiring diagrams to first wire the sensors and then apply power to the SureCross devices.

5-pin Euro-Style Wiring (Nodes)

Wiring the 5-pin Euro-style connector depends on the model and power requirements of the device. Connecting dc power to the commu-
nication pins will cause permanent damage. For FlexPower devices, do not apply more than 5.5V to the gray wire.

Wire No.

Wire Color

10 to 30V dc Powered Nodes

Battery Powered Nodes

1

2

3

4

5

1

Brown

10 to 30V dc

2

White

3

Blue

dc common (GND)

dc common (GND)

4

Black

5

Gray

3.6 to 5.5V dc

DX80...C Wiring

Wiring power to the DX80...C models varies depending the power requirements of the model. Connecting dc power to the communication
pins (Tx/Rx) will cause permanent damage. For FlexPower devices, do not apply more than 5.5V to the gray wire.

Terminal Label Gateway, DX85

10 to 30V dc Powered Nodes

Battery Powered Nodes

V+

10 to 30V dc

10 to 30V dc

Tx/+

RS485 / D1 / B / +

V-

dc common (GND)

dc common (GND)

dc common (GND)

Rx/-

RS485 / D0 / A / -

B+

3.6 to 5.5V dc

SureCross DX80 FlexPower Counter Node

4

www.bannerengineering.com - tel: 763-544-3164

P/N 136348 Rev. G