Modbus register table, Specifications – Banner SureCross DX80 Wireless Networks User Manual

Page 6

Advertising
background image

LED 1

LED 2

Node Status

(flashing green)

Radio Link Ok

(flashing red)

(flashing red)

Device Error

(flashing red, 1 per 3 sec)

No Radio Link

Modbus Register Table

I/O

Modbus Holding Register

I/O Type

Units

I/O Range

Holding Register
Representation

Terminal

Block Labels

Gateway or

DX85

Any Node

Min. Val-
ue

Max. Val-
ue

Min.
(Dec.)

Max.
(Dec.)

1

1

1 + (Node# × 16)

Discrete IN 1

-

0

1

0

1

DI1

2

2

2 + (Node# × 16)

Discrete IN 2

-

0

1

0

1

DI2

3

3

3 + (Node# × 16)

Discrete IN 3

-

0

1

0

1

DI3

4

4

4 + (Node# × 16)

Discrete IN 4

-

0

1

0

1

DI4

5

5

5 + (Node# × 16)

Analog IN 1

mA
V

0.0
0.0

20.0
10.0

0

65535

AI1

6

6

6 + (Node# × 16)

Analog IN 2

mA
V

0.0
0.0

20.0
10.0

0

65535

AI2

7

7

7 + (Node# × 16)

Reserved

8

8

8 + (Node# × 16)

Device Message

9

9

9 + (Node# × 16)

Discrete OUT 1

-

0

1

0

1

DO1

10

10

10 + (Node# × 16)

Discrete OUT 2

-

0

1

0

1

DO2

11

11

11 + (Node# × 16)

Discrete OUT 3

-

0

1

0

1

DO3

12

12

12 + (Node# × 16)

Discrete OUT 4

-

0

1

0

1

DO4

13

13

13 + (Node# × 16)

Analog OUT 1

mA
V

0.0
0.0

20.0
10.0

0

65535

AO1

14

14

14 + (Node# × 16)

Analog OUT 2

mA
V

0.0
0.0

20.0
10.0

0

65535

AO2

15

15

15 + (Node# × 16)

Control Message

16

16

16 + (Node# × 16)

Reserved

Some analog I/O models may use milliamps or voltage, depending on the model. Check the models table (on page 1) of your product's
data sheet to determine which model you have.

Specifications

Radio and General

Range

900 MHz: Up to 4.8 kilometers (3 miles)
2.4 GHz: Up to 3.2 kilometers (2 miles)

Power

Requirements: +10 to 30V dc (Outside the USA: +12 to
24V dc, ±10%). (See UL section below for any applica-
ble UL specifications)
Consumption: Less than 1.4 W (60 mA) at 24V dc

SureCross DX80 Node

6

www.bannerengineering.com - tel: 763-544-3164

P/N 131936 Rev. H

Advertising