VI. APPENDIX
Temperature Correction Factors
Deg C
Deg F
Correction Factor
30 86
1.16
29 84.2
1.13
28 82.4
1.09
27 80.6
1.06
26 78.8
1.03
25 77
1.00
24 75.2
0.97
23 73.4
0.94
22 71.6
0.92
21 69.8
0.89
20 68
0.86
19 66.2
0.84
18 64.4
0.81
17 62.6
0.79
16 60.8
0.77
15 59
0.74
14 57.2
0.72
13 55.4
0.70
12 53.6
0.68
11 51.8
0.66
10 50
0.64
9 48.2
0.62
8 46.4
0.61
7 44.6
0.59
6 42.8
0.57
5 41
0.55
Multiply the nominal product flow at 25° C by
the temperature correction factor to
determine the flow at various other
temperatures.