Bunn LCR-3 User Manual

Page 24

Advertising
background image

24

EVAP TEMP SENSOR

OUT OF RANGE

CHECK FOR BAD

CONNECTIONS

CHECK WIRE FOR

SHORTS

COOL TEMP SENSOR

OUT OF RANGE

CHECK FOR BAD

CONNECTIONS

CHECK WIRE FOR

SHORTS

COOLER FAULT!

EVAP TEMP TOO HI

CHECK EVAP FAN

CHK EVAP SENSOR

COOLING TIME

TOO LONG

CHECK AIR FILTER

CHECK COOLING UNIT

Service Required

Service Required

Service Required

Clean Air Filter

Check wiring harness for breaks,

shorts, open connectors

Service Required

Screen Displayed

Possible Cause

Troubleshooting Procedures

Troubleshooting (Continued)

Service Required

Service Required

Service Required

1. Evaporator temperature too high or too

low.

2. Corresponding Evaporator Sensor Probe

wire(s) broken or disconnected.

3. Corresponding Temperature Sensor

Probe wire(s) shorted to housing, or

to each other.

1. Cold Sensor wire(s) shorted to housing,

or to each other.

2. Product cabinet temperature too

high.

3. Product cabinet temperature too low.

COND PROBE FAULT

CHECK COND PROBES

CHK DISP SWITCHES

CHK CONNECTIONS

JUMPER FAULT!

CONFIG NOT VALID

CHECK J-18

ON CONTROL BOARD

1. Concentrate buildup on probes

2. Machine dispensing continously

3. Water flowing continously

1. Invalid wire harness configuation

Check pump & tubing for proper

installation. Clean probes

Dispense switch failure, Service

Required

Dispense valve leaking, Service

Required

Service Required

Service Required

Service Required

Service Required

1. Cabinet circulating fan failure

2. Ice build up on evaporator coils

3. Evaporator sensor failure

1. Air intake filter clogged

2. Wiring failure

3. Compressor failure

41129 052208