Kenco Engineering SmartSonic Transmitter (Remote) User Manual

Page 15

Advertising
background image

Page 15

Press / Action

Display

Description

Press ENT when “Relay” is flashing to enter
relay setup




or

For example:

Cycle between options until it displays FLOW

Press ENT to select the FLOW option




or then

Select the relay number you wish to configure,
then press ENT.


and

The appropriate relay number (Relay #1 in this
example), flashes throughout the process of
defining the values for the relay




and

This screen allows you to enter up to (4) digits
of High numbers of flow values.




and

This screen allows you to enter up to (5) digits
of Low numbers of flow values.

Repeat the previous steps to set a CLOSED
value for the relay.


In the example above, the relay values were configured in the following way:

00001 was entered in the High numbers (H = 1)

20000 was entered in the Low numbers (L = 20,000)

This would mean that the OPEN value was set at 120.000 (

G.P.M. or M

3

/HR)


NOTE: The same procedure is used for the Volume and Totalization Modes. The units for the Totalization Mode are
Gallons when the selected Measurement Unit is G.P.M. The units for the Volume Mode are the same used when entering
the Volume Strapping Table (see Additional Features Section later in this manual).

Setting Relay #4 to Report Errors
This allows you to use Relay #4 as a trigger to set an alarm if the unit has a “Lost Echo”, indicates a level higher than the
Tank Height, or when the level moves into the “Dead Zone”. Once the error mode is enabled, and an error occurs, the
relay will de-energize and the error message will show on the display. The following are the error displays:

EE EEE: Loss of Echo, or measurement value is greater than the Tank Height.

FF FFF: Process media is in the “Dead Zone”.


The relay will be energized as long as the unit is functioning properly.

Advertising