Пм ныокчэы ять уячтмытятэы росэыьлоын, Warning – Klimaire GM80S Series User Manual

Page 32

Advertising
background image

íð

I&O manual

пм НЫОКЧЭЫ ЯТЬ УЯЧТМЫТЯТЭЫ РОСЭЫЬЛОЫН

WARNING

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow safety warnings exactly could result in dangerous
operation, serious injury, death or property damage.

Improper servicing could result in dangerous operation, serious
injury, death or property damage.

Reconnect wires correctly.

WARNING

FIRE, EXPLOSION OR CARBON MONOXIDE POISONING
HAZARD

Failure to replace with proper control could result in fire,explosion or
carbon monoxide poisoning.

This appliance uses a NEGATIVE PRESSURE REGULATED gas
control.

Replace ONLY with the same model number or as specified by the
manufacturer.

пмтп Я²²«¿´ Ч²-°»½¬·±²

The furnace should be inspected by a qualified installer or service
agency at least once per year. This check should be performed at
the beginning of the heating season. This will ensure that all
furnace components are in proper working order and that the
heating system functions appropriately. Pay particular attention to
the following items. Repair or service as necessary.

(a) All flue gas carrying areas external to the furnace (i.e. chimney,
vent connector) are clear and free of obstructions.
(b) The vent connector is in place, slopes upward and is physically
sound without holes or excessive corrosion.
(c) The return-air duct connection(s) is physically sound, is sealed
to the furnace casing, and terminates outside the space containing
the furnace.
(d) The physical support of the furnace is sound without sagging,
cracks, gaps, etc, around the base so as to provide a seal between
the support and the base.
(e) There are no obvious signs of deterioration of the furnace.
(f) The pilot and burner flames are in good adjustment (by comparison
with pictorial sketches or drawings of the main burner flame and,
if applicable, the pilot burner flame).

пмто Ъ·´¬»®-

there

must be a means of filtering all of the return air. The installer will
supply filter(s) at the time of installation.

ЪЧФМЫО УЯЧТМЫТЯТЭЫ

Improper filter maintenance is the most common cause of inadequate
heating or cooling performance. Filters should be cleaned (permanent)
or replaced (disposable) every one month or as required.
When rep|acing a filter, it must be replaced with a filter of the same
type and size.

Become familiar with filter location and procedures for removal
cleaning and replacing them. If help is needed, contact the installer
of the furnace or a qualified servicer.

ЪЧФМЫО ОЫУСКЯФ

Depending on the installation, differing filter arrangements can
be applied. A media air filter or electronic air cleaner can be used
as an alternate filter.

Follow the filter sizes given in the Recommended Minimum Filter
size table to ensure proper unit performance.

For further details, see your distributor.

ЛРОЧЩШМ ЪЧФМЫО ОЫУСКЯФ

To remove filters from an external filter rack in an upright upflow
installation, follow the directions provided with external filter rack
kit.
Clean, wash and dry a permanent filter. When using a permanent
filter, both sides should be sprayed with a dust adhesive as
recommended on the adhesive container. Spray adhesives for
use with permanent filters can be found at some hardware stores.
BE SURE AIRFLOW DIRECTION ARROW POINTS TOWARDS
THE BLOWER.
Inspect filter. If your dirty filter is the disposable type, replace dirty
filter with the same type and size filter. If your dirty filter is a
permanent filter, clean as follows:

,

rinse, and dry the permanent filters. Both sides

should then be sprayed with a filter adhesive as is
recommended on the adhesive container. Many hardware
stores stock spray adhesives for use with permanent filters.

,

these filters must be replaced

by equal size permanent, high velocity filters. Throwaway
filters must not be used as replacement for permanent
filters. Under normal use, permanent filters should last for
several years.

пмтн ЧТЬЛЭЫЬ ЬОЯЪМ ЯТЬ ЭЧОЭЛФЯЧТЩ ЮФСЙЫО УСМСОН

The bearings in the induced draft blower and ciretdator blower
motors are permanently lubricated by the manufacturer. No further
lubrication is required. Check motor windings for accumulation
of dust which may cause overheating. Clean as necessary.

пмтм ЪФЯУЫ НЫТНСО шПЛЯФЧЪЧЫЬ НЫОКЧЭЫО СТФЗч

Under some conditions the fuel or air supply can create a nearly
invisible coating on the flame sensor. This coating acts as an
insulator causing a drop in the flame sense signal. If the flame
sense signal drops too low. the furnace will not sense flame and
will lock out. The flame sensor should be carefully cleaned by a
qualified servicer using emery cloth or steel wool. Following
cleaning the flame Sense signal should be 1 to 6 microamps at
115 volts.

ЧЩТЧМЫО шПЛЯФЧЪЧЫЬ НЫОКЧЭЫО СТФЗч

If the igniter and the surrounding air are at about 70°F and the
igniter wires are not connected to any other electrical components.
the resistance of the igniter should not exceed 200 ohms. If it
does the igniter should be replaced.

пмтл Ю«®²»®-

Periodically during the heating season make a visual check of
the burner flames. Turn the furnace on at the thermostat. Wait a
few minutes since any dislodged dust will alter the normal flame
appearance. Flames should be stable quiet soft and blue with
slightly orange tips. They should not be yellow. They should extend
directly outward from the burner ports without curling downward
floating or lifting off the ports. See Fig.30.

WARNING

To avoid personal injury or death. Do not remove any interal
compartment covers or attempt any adjustment. Electrical
compartments are contained in both compartments. Contact a
qualified service agent at once if an abnormal flame
appearance should develop.

FIRE, EXPLOSION, ELECTRICAL SHOCK,AND CARBON
MONOXIDE POISONING HAZARD

NOTE: Only a qualified contractor, installer or service agency
should clean the burners, if the burners get a heavy accumul-
ation of soot and carbon.

Advertising