03 input wiring specifications – Tweco CutMaster 101 User Manual

Page 14

Advertising
background image

INTRODUCTION

2-2

Manual 0-2852

Power Supply Dimensions & Weight

Ventilation Clearance Requirements

A-03572

27.5 in / 696 mm

12.4 in /
315 mm

17.3 in /
439 mm

83 lb / 37.6 kg

Art # A-03379

6"

150 mm

24"

0.6 m

6"

150 mm

6"

150 mm

2.03 Input Wiring Specifications

Input

Power Input

Current Input

Suggested Sizes (See Notes)

Voltage

Freq.

1-Ph

3-Ph

1-Ph

3-Ph

Fuse (Amps)

Wire (AWG)

Wire (Canada)

(Volts)

(Hz)

(kVA)

(kVA)

(Amps)

(Amps)

1-Ph

3-Ph

1-Ph

3-Ph

1-Ph

3-Ph

208

50

14.4

69

90

6

6

208

60

15.6

75

90

6

6

230

50

15

65

80

6

6

230

60

15.5

67

80

6

6

400

50/60

13.9

20

30

10

10

460

60

18

39

50

10

10

460

60

16

20

30

12

12

600

60

13.5

13

20

12

12

Line Voltages with Suggested Circuit Protection and Wire Sizes

Based on National Electric Code and Canadian Electrical Code

CutMaster 101 Input Wiring Specifications

NOTES

Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.

Cable size is de-rated based on the Duty Cycle of the equipment.

The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations
refer to local or national codes.

Cable conductor temperature used is 167° F (75° C).

An energy limiting fuse UL Class RK-1 (examples: BUSS LPS / LPN-RK or Gould-Shawmut AZK-A6K) should be
used to minimize damage to Plasma Cutting, Welding or power distribution equipment.

NEVER

use replaceable element fuses like UL Class H, or "one-time" fuses like UL Class K5.