Turbomachinery Package Specification

Titan

250 Generator Set

Minute Log

- data are read and stored at one-minute intervals for the previous 62 days,

one file for each day.

10 Second Log

- data are read at 10-second intervals for the previous 31 days, one file

for each day.

Trigger Log

- data are read at one-second intervals for 6 minutes before a “trigger” event

that is defined in the software. The standard trigger is a shutdown. Six minutes before the
trigger of data are written to a file. Up to 50 trigger logs files can be stored.

9.5.4

TT4000 Display Language

In addition to English, dual language screens are available with English and Spanish
(Latin America), Portuguese (Brazil), French, German or Chinese (simplified). Other
languages can be provided as custom features.

9.5.5

TT4000 Operating Modes

There are two operating modes for the TT4000 software: Design Time and Run Time.
Design Time is used to create or modify a project’s working files. Run Time uses those
files in the normal equipment operation.

9.5.6 Supervisory

Control

Interfaces

The Turbotronic 4 control system can transmit data to, and receive control instructions
from, a supervisory control system. All analog data and the status of all discrete values
are available for transmittal. Interface modules mount in the controller rack and connect
through the rack’s backplane. Available connections are:

• ControlLogix 1.5
• Ethernet
• Data Highway Plus
• Modbus

9.5.7 System

Programmability

The Turbotronic 4 system is fully programmable in the field. Programming requires a
licensed copy of Rockwell Automation’s RSLogix 5000 software installed on a suitable
computer with the corresponding interface card installed. Solar offers two standard
options:

Software, instruction manual, interface card and connecting cable.
Fully configured portable computer with the software, instruction manual, interface card and

connecting cable

9.5.8 Engineering

Units

The following engineering unit options are available for the screen displays:

Metric 1

Metric 2

Metric 3

English

Pressure

kPa bar

kg/cm

3

psig

Temperature

°C °C °C °F

© 2008 Solar Turbines Incorporated. All rights reserved.