9 co2 fire suppression system, 10 water mist fire suppression system, Figure 22 – CAT Titan 250 User Manual

Page 49: Typical fire and gas system

Advertising
background image

Turbomachinery Package Specification

Titan

250 Generator Set

The enclosure is also equipped with two gas detectors: one at the gas turbine enclosure
ventilation air inlet and the other at the ventilation exhaust to provide continuous
monitoring of combustible gases. The detectors consist of IR hydrocarbon sensors that
provide input to the logical operating network (LON) module. The gas turbine start signal
is interlocked with the combustible gas monitoring system to ensure the atmosphere is
safe prior to initiating a turbine engine start. An alarm is initiated if the gas monitor fails.

OPERATOR PANEL

EQP

DCIO

MIR

MIR

MIR

MIR

IR

IR

TD

TD

TD

TD

Turbotronic

4

Control

Processor

Turbotronic

4

Back-up

Shutdown

System

Turbomachinery Package

To / From Customer
Supervisory System

STROBES / HORN

FIRE

SUPPRESSION

SYSTEM

AUTO

INHIBIT

DISCHARGED

AUTO / INHIBIT

MANUAL RELEASE

LON

DCIO

MIR =

Multi-spectrum IR Flame Detector

TD

=

Thermal Detector

IR

=

IR Gas Detector

LON =

Local Operating Network

ControlNet

Figure 22. Typical Fire and Gas System

11.3.9 CO

2

Fire Suppression System

The enclosure can be equipped with a CO

2

fire suppression system consisting of a

primary total flooding distribution system and a secondary metered distribution system to
extend the design concentration of 37% CO

2

for 20 minutes.

On fire detection by the optional fire and gas detection system, the detectors transmit an
electrical signal via the fire control panel to activate the fire suppression system release
solenoids located in the CO

2

fire suppression cylinder cabinets (Figure 23). On receipt of

this signal, the solenoid actuated control heads activate the CO

2

cylinders, releasing CO

2

into the enclosure. CO

2

pressure actuates the pressure trip operated dampers that close

all vent openings. CO

2

release control heads are also provided with manual release

levers.

11.3.10 Water Mist Fire Suppression System

The enclosure can be equipped with a water mist (fine water spray) fire suppression
system consisting of a high-pressure distribution system to provide approximately 10
minutes continuous water discharge. The typical water mist fire suppression cylinder
cabinet (Figure 24) consists of two high-pressure nitrogen cylinders used as a propellant
and five water bottles.

© 2008 Solar Turbines Incorporated. All rights reserved.

TPS250GS/908 - Preliminary