• Reactive power (@25

°

C

±

5

°

C, R.H.

60% non-condensing):

±

0.5% (rdg + f.s.) (cos

ϕ

0.5 L/C, 0.1 to 1.2 In, range AV5) or

±

1% rdg (cos

ϕ

0.5 L/C, 0.1 to 1.2 In, range AV5).

• Apparent power (@25

°

C

±

5

°

C, R.H.

60% non-condensing):

±

0.5% (rdg + f.s.) (0.1 to 1.2 In, range AV5) or

±

1% rdg (0.1 to 1.2 In, range AV5).

• Energies (@25

°

C

±

5

°

C, R.H.

60% non-condensing):

class 1 according to EN61036 and EN61268. Ib: 5A,
Imax: 6A, 0.1 Ib: 500mA; start up current: 20mA; Un: 240V
(AV5), 400V (AV7).

• Harmonic distortion (@25

°

C

±

5

°

C, R.H.

60% non-con-

densing):
1% f.s. (f.s.:100%); phase:

±

2

°

; Imin: 0.1Arms; Imax: 15Ap;

Vmin: 50Vrms; Cmax: 500Vp; sampling frequency 6400Hz
@ 50Hz

ADDITIONAL ERRORS:
• Humidity:

0.3% rdg, 60% to 90% R.H.

• Magnetic field:

0.5% rdg, @ 400 A/m.

• Input frequency:

0.4% rdg, 62 to 400 H

Z

.

TEMPERATURE DRIFT:

200ppm/

°

C

SAMPLING RATE: 6400Hz @ 50Hz
DISPLAY:
Graphic, back-lighted LCD, 128x64 dots.
Selectable read-out for the instantaneous variables: 4 x 4 dgts
or 4 x 3

1

/

2

dgts.

Total energies: 4 x 9 dgts; Partial energies: 4 x 6 dgts
MAX. AND MIN. INDICATION:
Max. 9.999 (999.999.999), Min. -9.999 (-999.999.999)
MEASUREMENTS:
Current, voltage, power, energy, harmonic distortion (see list
of the displayed pages/variables). TRMS measurement of a
distorted sine wave voltage/current;
Connection type: direct
Crest factor:

3 max. 15Ap/500Vp (VL-N) or 15Ap/800Vp (VL-N)

Technical features