START-UP

Use the following information and Start-Up Checklist

on page CL-1 to check out unit PRIOR to start-up.

Unit Preparation —

Check that unit has been installed

in accordance with these installation instructions and appli-
cable codes.

Compressor Mounting —

Loosen the compressor hold-

down bolts until sidewise movement of the washer under
each holddown bolt head can be obtained. Do not loosen
completely as bolts are self-locking and will maintain
adjustment.

Internal Wiring —

Check all electrical connections in

unit control boxes; tighten as required.

Refrigerant Service Ports and Valves —

Each 48HJ

unit has 2 Schrader-type service ports per circuit; one on the
suction line and one on the liquid line. Be sure that the caps
on the ports are tight. The units also have 2 service valves
per circuit; one on the suction line and one on the discharge
line. Be sure all valves are open.

Crankcase Heater —

Crankcase heater is energized

as long as there is power to the unit.

IMPORTANT: Unit power must be on for 24 hours
prior to start-up. Otherwise, damage to compressor may
result.

Evaporator Fan —

Fan belt and pulleys are factory in-

stalled. See Tables 3A, 3B, 4, and 5 for Fan Performance
Data. Remove tape from fan pulley and adjust pulleys on
48HJ015 units as required. See Evaporator-Fan Perfor-
mance Adjustment section on page 19. Be sure that fans ro-
tate in the proper direction. See Table 6 for air quantity lim-
its. See Table 7 for static pressure drops for accessories and
options. See Fig. 23 and 24 for fan performance using hori-
zontal adapter and power exhaust. To alter fan performance,
see Performance Adjustment sections on page 19.

Condenser-Fans and Motors —

Condenser fans and

motors are factory set. Refer to Condenser-Fan Adjustment
section on page 20 as required. Be sure that fans rotate in the
proper direction.

Return-Air Filters —

Check that correct filters are in-

stalled in filter tracks (see Table 1). Do not operate unit with-
out return-air filters.

Outdoor-Air Inlet Screens —

Outdoor-air inlet screens

must be in place before operating unit.

Accessory Field-Installed Economizer Adjust-
ment —

Remove filter access panel. Check that outdoor-

air damper is closed and return-air damper is open.

Economizer operation and adjustment are described in

Base Unit Operation section on page 17; and Economizer
Adjustment section on page 20.

NOTES:
1. Dimensions are in millimeters.
2. The 50DP900211 high static regain adapter accessory may be used

to provide horizontal supply/return.

NOTE: The 50DP900211 horizontal supply/return adapter accessory
improves 48HJ fan performance by increasing external static pres-
sure by amount shown above.

Fig. 23 — Horizontal Supply/Return Fan Performance

With 50DP900211 High Static Regain Adapter

Fig. 22 — Outdoor-Air Hood Details