Carrier SINGLE PACKAGE ROOFTOP UNITS ELECTRIC COOLING/GAS HEATING 48HJ015-025 User Manual

Page 18

Advertising
background image

SERVICE

Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.

Cleaning —

Inspect unit interior at beginning of each heat-

ing and cooling season and as operating conditions require.
Remove unit top panel and/or side panels for access to unit
interior.

MAIN AND PILOT BURNERS — At the beginning of each
heating season, inspect for deterioration or blockage due to
corrosion or other causes. Observe the pilot and main burner
flames through view port (in condenser section), and adjust
if necessary. Refer to Pilot Adjustment or Main Burners sec-
tions on pages 22 and 23.

FLUE GAS PASSAGEWAYS — The flue collector box and
heat exchanger cells may be inspected by removing heat ex-
changer access panel (Fig. 4 and 5), flue box cover, and main
burner assembly (Fig. 25). Refer to Main Burners section on
page 23 for burner removal sequence. If cleaning is re-
quired, remove heat exchanger turbulators (Fig. 26) and clean
all parts with a wire brush.

COMBUSTION-AIR BLOWER — Clean periodically to as-
sure proper airflow and heating efficiency. Inspect blower
wheel every fall and periodically during heating season. For
the first heating season, inspect blower wheel bi-monthly to
determine proper cleaning frequency.

To inspect blower wheel, remove heat exchanger access

panel. Shine a flashlight into opening to inspect wheel. If
cleaning is required, remove motor and wheel assembly by
removing screws holding motor mounting plate to top of com-
bustion fan housing (Fig. 25 and 26). The motor and wheel
assembly will slide up and out of the fan housing. Remove
the blower wheel from the motor shaft and clean with a de-
tergent or solvent. Replace motor and wheel assembly.

EVAPORATOR COIL — Clean as required with commer-
cial coil cleaner.

CONDENSER COIL — Clean condenser coil annually and
as required by location and outdoor-air conditions. Inspect
coil monthly; clean as required.
CONDENSATE DRAIN — Check and clean each year at
start of cooling season. In winter, keep drains and traps dry.

FILTERS — Clean or replace at start of each heating and
cooling season, or more often if operating conditions re-
quire. Refer to Table 1 for type and size.
OUTDOOR-AIR INLET SCREENS — Clean screens with
steam or hot water and a mild detergent. Do not use dis-
posable filters in place of screens.

Lubrication

COMPRESSORS — Each compressor is charged with the
correct amount of oil at the factory. Observe the level in the
sight glass immediately after shutdown while the oil is still
warm. If the oil level is observed when the oil is cold, the
level observed may be a mixture of oil and refrigerant which
is not a true indication of the oil level. If oil level observed
is not between the low limit and high limit levels as indi-
cated in Fig. 27, add oil until it is in the correct range.

Fig. 25 — Typical Gas Heating Section

(48HJE015, 48HJE017, and 48HJD025 Shown)

Fig. 26 — Typical Heating Section With

Main Burners Removed

(48HJE015, 48HJE017, and 48HJD025 Shown)

Fig. 27 — Compressor Sight Glass Oil Level

18

Advertising