MAXIMUM SHIPPING WEIGHT

Lb

Kg

2535

1150

NOTES:
1. Dimensions in (

) are in millimeters.

2.

Center of gravity.

3.

Direction of airflow.

4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance:

a. Rear: 7

Ј

0

Љ

(2134) for coil removal. This dimen-

sion can be reduced to 4

Ј

0

Љ

(1219) if conditions

permit coil removal from the top.

b. 4

Ј

0

Љ

(1219) to combustible surfaces, all four sides

(includes between units).

c. Left side: 4

Ј

0

Љ

(1219) for proper condenser coil

airflow.

d. Front: 4

Ј

0

Љ

(1219) for control box access.

e. Right side: 4

Ј

0

Љ

(1219) for proper operation of

damper and power exhaust (if so equipped).

f. Top: 6

Ј

0

Љ

(1829) to assure proper condenser fan

operation.

g. Bottom: 14

Љ

(356) to combustible surfaces (when

not using curb).

h. Control box side: 3

Ј

0

Љ

(914) to ungrounded sur-

faces (non-combustible).

i. Control box side: 3

Ј

6

Љ

(1067) to block or concrete

walls, or other grounded surfaces.

j. Local codes or jurisdiction may prevail.

6. With the exception of clearance for the condenser

coil and the damper/power exhaust as stated in Note
No. 5, a removable fence or barricade requires no
clearance.

7. Dimensions are from outside of corner post. Allow

0

Ј

-

5

16

Љ

(8) on each side for top cover drip edge.

CORNER WEIGHT*

A

B

C

D

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

523

237

541

245

574

260

596

270

*Weights are for unit only and do not include options or crating.

Fig. 5 — Base Unit Dimensions, 48HJ025