Failure to follow these precautions could result in damage to
the unit being installed:
1. Make all electrical connections in accordance with NEC

ANSI/NFPA (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical connec-
tions must be in accordance with CSA standard C22.1
Canadian Electrical Code Part 1 and applicable local
codes. Refer to unit wiring diagram.

2. Use only copper conductor for connections between

field-supplied electrical disconnect switch and unit. DO
NOT USE ALUMINUM WIRE.

3. Be sure that high-voltage power to unit is within operating

voltage range indicated on unit rating plate.

4. Do not damage internal components when drilling through

any panel to mount electrical hardware, conduit, etc. On
3-phase units, ensure phases are balanced within 2 percent.
Consult local power company for correction of improper
voltage and/or phase imbalance.

HIGH-VOLTAGE CONNECTIONS
The unit must have a separate electrical service with a field-
supplied, waterproof, disconnect switch mounted at, or within
sight from, the unit. Refer to the unit rating plate for maximum
fuse/circuit breaker size and minimum circuit amps (ampacity) for
wire sizing. See Tables 4 and 5 for electrical data.
The field-supplied disconnect switch box may be mounted on the
unit over the high-voltage inlet hole when the standard power and
low-voltage entry points are used. See Fig. 2 & 3 for acceptable
location.
See unit wiring label and Fig. 10 for reference when making high
voltage connections. Proceed as follows to complete the high-
voltage connections to the unit.
Single phase units:

1. Run the high-voltage (L1, L2) and ground leads into the

control box.

2. Connect ground lead to chassis ground connection.
3. Connect L1 to pressure lug connection 11 of the compressor

contactor.

4. Connect L2 to pressure lug connection 23 of the compressor

contactor.

Three phase units:

1. Run the high-voltage (L1, L2, L3) and ground leads into the

control box.

2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the lines side

of the contactor.

4. Connect field L1 to black wire on connection 11 of the

compressor contactor.

5. Connect field wire L2 to yellow wire on connection 13 of the

compressor contactor.

6. Connect field wire L3 to Blue wire from compressor.

SPECIAL PROCEDURES FOR 208-V OPERATION

Make sure that the power supply to the unit is switched OFF
and lockout tag installed before making any wiring changes.
Electrical shock can cause serious injury or death.

CONTROL VOLTAGE CONNECTIONS

NOTE: Do not use any type of power-stealing thermostat. Unit
control problems may result.
Use no. 18 American Wire Gage (AWG) color-coded, insulated
(35 C minimum) wires to make the control voltage connections
between the thermostat and the unit. If the thermostat is located
more than 100 ft. from the unit (as measured along the control
voltage wires), use no. 16 AWG color-coded, insulated (35 C
minimum) wires.

STANDARD CONNECTION
Remove knockout hole located in the electric heat panel adjacent
to the control access panel. See Fig. 2 & 3. Remove the rubber
grommet from the installer’s packet (included with unit) and install
grommet in the knockout opening. Provide a drip loop before
running wire through panel.

Fig. 9—Vertical Duct Cover Removed

C99012

DUCT COVERS REMOVED

Fig. 10—High- and Control-Voltage Connections

C99010

POWER

SUPPLY

FIELD-SUPPLIED

FUSED DISCONNECT

HIGH VOLTAGE

POWER LEADS

(SEE UNIT WIRING

LABEL)

GND

CONTROL BOX

SPLICE BOX

LOW-VOLTAGE

POWER LEADS

(SEE UNIT

WIRING LABEL)

Y

G

R

C

YEL(Y)

GRN(G)

RED(R)

BRN(C)

THERMOSTAT

(TYPICAL)

LEGEND

Field Control-Voltage Wiring

Field High-Voltage Wiring

NOTE: Use blue wire for 3-phase units only.

10