Run the low-voltage leads from the thermostat, through the inlet
hole, and into unit low-voltage splice box.
Locate five 18-gage wires leaving control box. These low-voltage
connection leads can be identified by the colors red, green, yellow,
brown, and white (See Fig. 10). Ensure the leads are long enough
to be routed into the low-voltage splice box (located below right
side of control box). Stripped yellow wire is located in connection
box. Route leads through hole in bottom of control box and make
low-voltage connections (See Fig. 10). Secure all cut wires, so that
they do not interfere with operation of unit.
TRANSFORMER PROTECTION
The transformer is of the energy-limiting type. It is set to
withstand a 30-second overload or shorted secondary condition.

PRE-START-UP

Failure to observe the following warnings could result in
serious personal injury:
1. Follow recognized safety practices and wear protective

goggles when checking or servicing refrigerant system.

2. Do not operate compressor or provide any electric power to

unit unless compressor terminal cover is in place and
secured.

3. Do not remove compressor terminal cover until all electri-

cal sources are disconnected.

4. Relieve and recover all refrigerant from system before

touching or disturbing anything inside terminal box if
refrigerant leak is suspected around compressor terminals.

5. Never attempt to repair soldered connection while refrig-

erant system is under pressure.

6. Do not use torch to remove any component. System

contains oil and refrigerant under pressure. To remove a
component, wear protective goggles and proceed as fol-
lows:
a. Shut off electrical power to unit.
b. Relieve and reclaim all refrigerant from system using

both high- and low-pressure ports.

c. Cut component connecting tubing with tubing cutter and

remove component from unit.

d. Carefully unsweat remaining tubing stubs when neces-

sary. Oil can ignite when exposed to torch flame.

Proceed as follows to inspect and prepare the unit for initial
startup:

1. Remove access panel.
2. Read and follow instructions on all WARNING, CAUTION,

and INFORMATION labels attached to, or shipped with, unit.

3. Make the following inspections:

a. Inspect for shipping and handling damages such as broken

lines, loose parts, disconnected wires, etc.

b. Inspect for oil at all refrigerant tubing connections and on

unit base. Detecting oil generally indicates a refrigerant

C99024

452 = 5 v

457 = 7 v

455 = 2 v

LEGEND

FLA

— Full Load Amps

LRA

— Locked Rotor Amps

MCA

— Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection

RLA

— Rated Load Amps

NOTES:

1. In compliance with NEC (National Electrical Code) requirements

for multimotor and combination load equipment (refer to NEC

Articles 430 and 440), the overcurrent protective device for the

unit shall be Power Supply fuse . Canadian units may be

fuse or circuit breaker.

2. Minimum wire size is based on 60 C copper wire. If other than

60 C wire is used, or if length exceeds wire length in table,

determine size from NEC.

3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt-

age is greater than 2%. Use the following formula to determine

the percentage of voltage imbalance.
% Voltage imbalance

max voltage deviation from average voltage

= 100 x

average voltage

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

452 + 464 + 455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.

(AB) 457

(BC) 464

(AC) 457

Maximum deviation is 7 v.
Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the

maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is

more than 2%, contact your local electric utility company

immediately.

®

CKT BKR — Circuit Breaker