Accessory lifting kit is only to be used with Small Packaged
units which have a composite base pan with molded rigging
holds.

INSPECTION
Prior to initial use, and at monthly intervals, all rigging brackets
and straps should be visually inspected for any damage, evidence

of wear, structural deformation, or cracks. Particular attention
should be paid to excessive wear at hoist hooking points and load
support areas. Brackets or straps showing any kind of wear in these
areas must not be used and should be discarded.

INSTALLATION

1. Position the lifting bracket assembly around the base of the

unit. Leave the top shipping skid on the unit to act as a
spreader bar. Be sure the strap does not twist.

Fig. 2— 50GS018-042 and 50GX024-036 Unit Dimensions

UNIT

ELECTRICAL CHARACTERISTICS

UNIT WEIGHT

UNIT HEIGHT

IN. (MM)

”A”

CENTER OF GRAVITY

IN. (MM)

lb.

kg

X

Y

Z

50GS018

208/230-1-60

254

115.2

35.02 (889.5)

20.0 (508.0)

13.0 (330.2)

15.0 (381.0)

50GS024

208/230-1-60

260

117.9

35.02 (889.5)

19.0 (482.6)

13.0 (330.2)

15.0 (381.0)

50GS030

208/230-1-60, 208/230-3-60

258

117.0

35.02 (889.5)

19.0 (482.6)

14.0 (355.6)

15.0 (381.0)

50GS036

208/230-1-60, 208/230-3-60, 460-3-60

268

121.6

37.02 (940.3)

20.0 (508.0)

14.0 (355.6)

13.0 (330.2)

50GS042

208/230-1-60, 208/230-3-60, 460-3-60

294

133.3

35.02 (889.5)

19.0 (482.6)

14.0 (355.6)

13.0 (330.2)

50GX024

208/230-1-60

270

122.5

37.02 (940.3)

18.5 (469.9)

14.5 (368.3)

16.0 (406.4)

50GX030

208/230-1-60, 208/230-3-60

291

132.0

39.02 (991.1)

19.5 (495.3)

15.5 (393.7)

17.6 (447.0)

50GX036

208/230-1-60, 208/230-3-60, 460-3-60

299

135.6

35.02 (889.5)

19.5 (495.3)

15.25 (387.4)

16.5 (419.1)

C99007

REQUIRED CLEARANCE FOR OPERATION AND SERVICING

INCHES [mm]

EVAP. COIL ACCESS SIDE............................................................36.00 [914.0]

POWER ENTRY SIDE....................................................................42.00 [1066.8]

(EXCEPT FOR NEC REQUIREMENTS)

UNIT TOP .......................................................................................48.00 [1219.2]

SIDE OPPOSITE DUCTS ..............................................................36.00 [914.0]

DUCT PANEL .................................................................................12.00 [304.8] *

*MINIMUM DISTANCES: IF UNIT IS PLACED LESS THAN 304.8 [12.00] FROM

WALL SYSTEM, THEN SYSTEM PERFORMANCE MAYBE COMPROMISE.

REQUIRED CLEARANCE TO COMBUSTIBLE MATL.

INCHES [mm]

TOP OF UNIT...................................................................................14.00 [355.6]

DUCT SIDE OF UNIT.........................................................................2.00 [50.8]

SIDE OPPOSITE DUCTS ................................................................14.00 [355.6]

BOTTOM OF UNIT .............................................................................0.50 [12.7]

ELECTRIC HEAT PANEL .................................................................36.00 [914.4]

NEC. REQUIRED CLEARANCES.

INCHES [mm]

BETWEEN UNITS, POWER ENTRY SIDE ....................................42.00 [1066.8]

UNIT AND UNGROUNDED SURFACES, POWER ENTRY SIDE .36.00 [914.0]

UNIT AND BLOCK OR CONCRETE WALLS AND OTHER

GROUNDED SURFACES, POWER ENTRY SIDE.........................42.00 [1066.8]

3