Carrier PC 111 User Manual

Controls operation, and troubleshooting

Advertising
background image

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

PC 111

Catalog No. 534-763

Printed in U.S.A.

Form 48/50F,J-3T

Pg 1

3-00

Replaces: 48/50F,J-1T

Book 1

1

Tab

1a 1b

Controls Operation,

and Troubleshooting

CONTENTS

Page

SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 2
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
Rooftop Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
VAV Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Processor Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
• P1 — SUPPLY-AIR SET POINT
• P2 — ECONOMIZER POSITION
• P3 — RESET LIMIT
• P4 — DEMAND LIMIT
• P5 — ECONOMIZER MINIMUM POSITION
• P6 — WARM-UP SET POINT
• P7 — SASP RESET TEMPERATURE
• PROCESSOR BOARD OUTPUTS
• CONFIGURATION HEADER AND DIP SWITCH

ASSEMBLY

Relay Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Display Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
• T1 — SUPPLY-AIR TEMPERATURE THERMISTOR
• T2 — RETURN-AIR TEMPERATURE THERMISTOR
• T3 — SATURATED CONDENSING TEMPERATURE,

CIRCUIT 1

• T4 — SATURATED CONDENSING TEMPERATURE,

CIRCUIT 2

• T10 — RESET TEMPERATURE
Compressor Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
• CONTROL RELAY (CR)
Accessory Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
• P3 — RESET LIMIT
• P5 — ECONOMIZER MINIMUM POSITION
• P6 — MORNING WARM-UP TEMPERATURE
Single-Step Demand Unit. . . . . . . . . . . . . . . . . . . . . . . . . 7
Demand Limit Control Module (DLCM) . . . . . . . . . . . 7
Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
• ENTHALPY CONTROL
• DIFFERENTIAL ENTHALPY
Supply Fan Variable Frequency Drive (VFD). . . . . 12
High Capacity Modulating Power

Exhaust Variable Frequency Drive . . . . . . . . . . . . 12

Temperature Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
CONTROLS INSTALLATION . . . . . . . . . . . . . . . . . . 13-25
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
• NIGHT SETBACK THERMOSTAT
• SPACE TEMPERATURE RESET ACCESSORY

(50DJ900021)

Space Temperature Reset . . . . . . . . . . . . . . . . . . . . . . 13
• INSTALLATION
• CONFIGURATION
• OPERATING SEQUENCE
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
• SINGLE-STEP DEMAND LIMIT
• TWO-STEP DEMAND LIMIT
• INSTALLATION
• CONFIGURATION
• OPERATING SEQUENCE

Page

Control From Remote Building Management

System (BMS). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

• OCCUPIED/UNOCCUPIED
• NIGHT SETBACK CONTROL
• UNIT SUPPLY AIR SET POINT ADJUSTMENT
• DEMAND UNIT (1-STAGE OR 2-STAGE)
• SUPPLY DUCT PRESSURE SET POINT ADJUSTMENT
• EXTERNAL ALARM SIGNAL
• REMOTE ECONOMIZER CONTROL
Smoke Control Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . 21
• FIRE SHUTDOWN MODE
• PRESSURIZATION MODE
• EVACUATION MODE
• SMOKE PURGE MODE
• INSTALLATION
• CONFIGURATION
• OPERATING SEQUENCE
Air Pressure Tubing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
• INLET GUIDE VANES
• SUPPLY FAN VARIABLE FREQUENCY DRIVE
• MODULATING POWER EXHAUST
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-31
Initial Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Configuration Header . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
DIP Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Adjusting Set Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Potentiometers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Supply Fan Control with IGV Option . . . . . . . . . . . . 28
Supply Fan Control with VFD Option . . . . . . . . . . . . 28
Modulating Power Exhaust Option or

Accessory) (48FK,JK and 50FK,JK Units) . . . . . 30

High Capacity Power Exhaust

(48FM and 50FM,FS Units) . . . . . . . . . . . . . . . . . . . . 30

START UNIT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-34
Quick Test Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
OPERATING INFORMATION. . . . . . . . . . . . . . . . . . 34-44
Digital Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
• CODES 0 THROUGH 8, CAPACITY STEPS
• CODES 20 THROUGH 30 AND 88, OPERATIONAL

STATUS

• CODES 51 THROUGH 87, DIAGNOSTIC

INFORMATION

Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
• SIZE 034, 038 AND 048-088 UNITS
• SIZE 044 UNITS
• SIZE 104 UNITS
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Supply Fan Control with IGV . . . . . . . . . . . . . . . . . . . . 38
Supply Fan Control with VFD. . . . . . . . . . . . . . . . . . . . 38
Modulating Power Exhaust (48FK,JK and

50FK,JK Units Option or Accessory) . . . . . . . . . . 38

High Capacity Modulating Power Exhaust

(48FM and 50FM,FS Units) . . . . . . . . . . . . . . . . . . . . 38

Unit Staging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

48FK,JK034-104

48FM078-104

50FK,FY,JK,JY034-104

50FM,FS078-104

Variable-Air Volume Rooftop Units