Dell UPS 5600R User Manual

Page 29

Advertising
background image

29

Installation

|

5

Insert the conduit through the wiring access entry and attach the conduit fitting to the panel.
Strip 0.5” (1.5 cm) of insulation from the end of each incoming wire.

CAUTION:

If the UPS does not have an automatic protection device against current backfeed, Dell

recommends installing an external isolating device (see Figure 19). After the device is installed, you must add
a warning label with the following wording or the equivalent on the external AC contactor:
RISK OF VOLTAGE BACKFEED. Isolate the UPS before operating on this circuit, then check for hazardous
voltage between all terminals.

External Distribution Panel

UPS

L/L1

L/L1

N/L2

N/L2

Legend

Coil Remote Switch
Magneto-Thermal Input Main Switch
AC Contactor ( see Table 1)
Neutral/L2
L1 Line Input

B
Q

T
N/L2
L/L1

B

Q

T

Figure 19. Typical External Isolating Device Installation

The following table lists AC contactors that can be used as backfeed protection devices.

Table 1. Backfeed Protection Devices

Manufacturer

Type

Rating

Tianshui 213 Electrical Apparatus Co., Ltd.

(E203071)

GSC1(CJX4-d)-4011

220-240 Vac, 42 FLA

Moeller GMBH

DILM(C)32-10

600 V, 40A

LS Industrial Systems Co., Ltd. (E108780)

GMC(D)-32

600 Vac, 45A