Dell UPS 5600R User Manual

Page 44

Advertising
background image

44

|

Operation

Table 7. Settings (continued)

Description

Default Setting

Available Settings

Battery Saving Mode

[Disabled] [10%] [20%] [30%]...[100%]

The UPS output is turned off in five minutes if the
UPS is on battery and output power is below the
selected level.

Disabled

On Battery Notice Delay

[0s] [1s] [2s]...[99s]

The UPS issues a “UPS on battery” notice in the
specified number of seconds after the UPS starts to
discharge the batteries.

0s

Site Wiring Fault Alarm

[Enabled] [Disabled]

Disabled for 208V
models; Enabled for
all others

Bypass Voltage Low Limit

[-6%] [-7%]...[-20%] of nominal

The Bypass operation is disabled if the measured
bypass voltage level is below the nominal output
voltage (-15%).

NOTE:

The Qualify Bypass setting may overrule the

Bypass Voltage Low Limit setting.

-15% of nominal

Bypass Voltage High Limit

[+6%] [+7%]...[+20%] of nominal

The Bypass operation is disabled if the measured
bypass voltage level is above the nominal output
voltage (+10%).

NOTE:

The Qualify Bypass setting may overrule the

Bypass Voltage High Limit setting.

+10% of nominal

Qualify Bypass

[Always] [Never] [Bypass Disabled]

If Always, Bypass operation is allowed when:

S Bypass voltages > the value set for Bypass

Voltage Low Limit

S Bypass voltages < the value set for Bypass

Voltage High Limit

S Bypass frequency > (nominal frequency -3 Hz)
S Bypass frequency < (nominal frequency +3 Hz)
S Inverter is synchronized with Bypass when

unsynchronized transfers are disabled by the
value set for Unsynchronized Transfers

If Never, Bypass operation is always allowed; voltage
and frequency limits are not in use.

If Bypass Disabled, Bypass operation is prohibited.

Always