Installation

6

Connect the input and ground wires to the terminal block according to Figure 20 and Table 2.

Terminal Position

1

2

3

Figure 20. UPS Input Terminal Block

Table 2. UPS Wiring Specifications

Wire Function

Terminal

Position

UPS Wire Function

Terminal Wire

Size Rating*

Tightening Torque

Input

1

Input Ground

5.26–16 mm

2

(10–6 AWG)

2.49 Nm (22 lb in)

2

L2/Neutral In

3

L1 In

* Use a minimum:

S 10 AWG for equipment grounding wire, 75_C copper wire minimum
S 8 AWG for input line and neutral wires, 75_C copper wire minimum

7

Replace the terminal block cover.

8

Continue to the following section, “UPS Initial Startup.”