MIB Objects

Table 14. Product Physical Group Variables (continued)

Variable Name and Description

Variable

Unit

Variable

Type

OID

physicalBatteryABMStatus

Advanced Battery Monitoring status:

1: ABM charging

2: ABM discharging

3: ABM floating

4: ABM resting

5: ABM off

UPS.BatterySystem.Charger.Mode

5.1

Integer

physicalBatteryTestStatus

Battery test status:

S Done and Passed
S Done and Warning
S Done and Error
S Aborted
S In progress
S Not implemented
S Scheduled

UPS.BatterySystem.Battery.Test

5.2

Integer

physicalBatterySecondsRemaining

Battery remaining time calculated by the autonometer.

UPS.PowerSummary.RunTimeToEmpty

5.3

Integer

Seconds

physicalLoadSegment1ShutdownAfterDelay

Number of seconds remaining until load segment 1 switches off. -1 if no shutdown
countdown is in effect.

UPS.OutletSystem.Outlet[2].DelayBeforeShutdown

6.1

Integer

Seconds

physicalLoadSegment1StartupAfterDelay

Number of seconds remaining until load segment 1 switches on. -1 if no startup
countdown is in effect.

UPS.OutletSystem.Outlet[2].DelayBeforeStartup

6.2

Integer

Seconds