Site requirement guidelines, Rack-mounting guidelines – Cisco XR 12410 User Manual

Page 56

Advertising
background image

Chapter 2 Preparing for Installation

Site Requirement Guidelines

2-6

Cisco XR 12410 and Cisco XR 12810 Router Installation Guide

OL-17441-01

Site Requirement Guidelines

The following sections contain the site requirement guidelines that you should be
familiar with before installing the router:

Rack-Mounting Guidelines, page 2-6

Air Flow Guidelines, page 2-12

Temperature and Humidity Guidelines, page 2-13

Power Connection Guidelines, page 2-13

NEBS Supplemental Unit Bonding and Grounding Guidelines, page 2-18

Site Wiring Guidelines, page 2-20

Rack-Mounting Guidelines

The router can be mounted in most 2-post, 4-post, or telco-type 19-inch
equipment racks that comply with the Electronics Industries Association (EIA)
standard for equipment racks (EIA-310-D). The rack must have at least two posts
with mounting flanges to mount the router chassis. The distance between the
center lines of the mounting holes on the two mounting posts must be 18.31 inches
± 0.06 inch (46.50 cm ± 0.15 cm). The rack-mounting hardware included with the
router is suitable for most 19-inch equipment racks or telco-style frames.

Figure 2-2

shows examples of typical 2-post, 4-post, and telco-type equipment

racks.