Installation and Operation Handbook

Configuration

2408 and 2404 Controller

6-21

Name

Description

Values

Meaning

CAL

Calibration

In this mode you can
1. Calibrate the instrument using a mV source -

rcAL

or ref source

cal.

2. Offset the calibration to account for errors in actual sensor

measurement and a ref sensor -

UCAL

or user calibration

3. Return to factory set calibration -

FACT

or factory set calibration.

rcAL Calibration

point

nonE No calibration

PV

Calibrate main Process Value input.

PV.2

Calibrate DC input, or PV 2.

1A.Hi

Calibrate DC output high - Module 1

1A.Lo

Calibrate DC output low - Module 1

2A.Hi

Calibrate DC output high - Module 2

2A.Lo

Calibrate DC output low - Module 2

3A.Hi

Calibrate DC output high - Module 3

3A.Lo

Calibrate DC output low - Module 3


I

NPUT

C

ALIBRATION

For

CAL

=

PV’, or ‘PV.2

’, the following parameters apply.

PV

PV Calibration Value

IdLE

Idle

mv.L

Select 0mV as the calibration point

mv.H

Select 50mV as the calibration point

V 0

Select 0Volt as the calibration point

1. Select calibration value

V 10

Select 10V as the calibration point

2. Apply specified input

CJC

Select 0

o

C CJC calibration point

3. Press to step to

GO’ rtd

Select 400

Ω as the calibration point

HI 0

High impedance: 0Volt cal’n point

HI 1.0 High impedance: 1.0 Volt cal’n point

See Note below.

FACt

Restore factory calibration

GO

Start calibration

no

Waiting to calibrate PV point

Select

YES’ with

or

YES

Start calibration

Wait for calibration to

buSy

Busy calibrating

complete.

donE

PV input calibration completed

FAIL

Calibration failed

Note. When a DC input module is installed for the first time, or there is a requirement to change one,
then the microprocessor in the controller needs to read the factory calibration data stored in the module.
Select ‘

FACt’ as the calibration value. Step to ‘GO’ and start calibration.

Goto User
calibration table-
See also chapter 7

Go to input
Calibation table

Go to
DC Output
Calibration
table