Load Current Monitoring and Diagnostics

Installation and Operation Handbook

8-8

2416 Controller

8.8

TO CONFIGURE LOW AND HIGH CURRENT TRIP ALARMS

Alarm 1 will be configured as Load Current Low (

Lcr)

Alarm 2 will be configured as Load Current High (

Hcr)

Do This

This Is The Display You Should See

Additional Notes

Press

button

until the

AL Conf

is displayed

This opens the
configuration list
which contains the
Alarms

Press

to show

AL1 (alarm 1)

Press

or

to show

LCr

To select alarm 1

To make alarm 1 =
Low Current

Press

until

AL2 (alarm 2)
appears

Press

or

to show

HCr

After 0.5 sec the display
will blink to show the
alarm type has been
accepted

To select alarm 2.

To make alarm 2 =
High Current


Note:- The above alarms are known as SOFT ALARMS because they are indication
only.

AL

Conf

AL1

LCr

AL2

HCr