Condenser fans and motors, Return-air filters, Outdoor-air inlet screens – Carrier SINGLE PACKAGE ROOFTOP UNITS 48PG20-28 User Manual

Page 19: Gas heat

Advertising
background image

19

Condenser Fans and Motors —

Condenser fans and

motors are factory set. Refer to Condenser-Fan Adjustment
section (page 49) as required.

Return-Air Filters —

Check that correct filters are in-

stalled in filter tracks (see Table 1). Do not operate unit without
return-air filters.
NOTE: For units with 4-in. filter option, units are shipped with
standard 2-in. filters. To install 4-in. filters, the filter spacers
must be removed.

Outdoor-Air Inlet Screens —

Outdoor-air inlet screens

must be in place before operating unit.

Gas Heat —

Verify gas pressures before turning on heat as

follows:

1. Turn off field-supplied manual gas stop, located external

to unit.

2. Connect pressure gage to supply gas tap, located on field-

supplied manual shutoff valve (see Fig. 14).

3. Connect pressure gage to manifold pressure tap.
4. Turn on field-supplied manual gas stop. Temporarily

install the jumper wire between “R” and “W1” on TB2.
Set thermostat to HEAT and raise set point until heat
comes on.

5. After the unit has run for several minutes, verify the sup-

ply gas pressure is between 5.5 in. wg to 13.0 in. wg, and
the manifold pressure is 2.95 in. wg on horizontal dis-
charge applications and 3.00 on vertical discharge appli-
cations. If manifold pressure must be adjusted, refer to
Gas Valve Adjustment section.
NOTE: Supply gas pressure must not exceed 13.0 in. wg.

6. Set thermostat to OFF.
7. Remove jumper wire if the unit will be operating under

thermostat mode.

8. Return thermostat to desired set point.

Table 5 — Fan Performance — 48PGD20 Vertical Supply/Return Units

LEGEND

Boldface indicates field-supplied motor/drive required.

NOTES:
1. Motor drive ranges:

(A) Low Range: 685-939 rpm, 4.26 bhp (208/230 and 460-v), 751-954 rpm, 5.75 bhp (575-v)
(B) Mid-Low Range: 949-1206 rpm, 5.75 bhp
(C) Mid-High Range: 941-1176 rpm, 8.63 bhp
(D) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.

2. See page 36 for general fan performance notes.

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

5000

590

1.47

663

1.74

727

2.01

786

2.26

840

2.52

5500

633

1.82

703

2.11

764

2.40

820

2.67

872

2.94

6000

677

2.21

744

2.53

803

2.84

857

3.13

907

3.42

6500

722

2.67

786

3.01

842

3.33

894

3.64

942

3.95

7000

767

3.17

828

3.53

883

3.88

933

4.21

979

4.53

7500

813

3.74

871

4.12

924

4.48

972

4.83

1017

5.18

8000

859

4.36

915

4.77

966

5.15

1012

5.52

1056

5.88

8500

906

5.05

959

5.47

1008

5.87

1053

6.26

1096

6.64

9000

952

5.81

1004

6.25

1051

6.67

1095

7.07

1136

7.47

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

5000

891

2.77

940

3.02

987

3.27

1032

3.52

1076

3.77

5500

921

3.21

968

3.48

1014

3.74

1057

4.01

1099

4.27

6000

954

3.70

999

3.99

1042

4.27

1084

4.55

1125

4.83

6500

988

4.25

1032

4.55

1073

4.85

1114

5.14

1153

5.44

7000

1024

4.85

1066

5.17

1106

5.48

1145

5.79

1183

6.10

7500

1060

5.51

1101

5.84

1140

6.17

1178

6.50

1215

6.82

8000

1098

6.23

1138

6.58

1176

6.92

1213

7.26

1249

7.60

8500

1137

7.01

1175

7.38

1212

7.74

1248

8.09

1283

8.45

9000

1176

7.86

1214

8.24

1250

8.61

1285

8.99

1319

9.36

Bhp — Brake Horsepower Input to Fan

A

B

C

D

B

B

B

B

C

C

C

D

D

D

A

A

A

A

A

B

B

B

B

C

C

C

C

C