Table 22 — Fan Performance — 48PGF28 — Horizontal Supply and Return Units

LEGEND

Boldface indicates field-supplied motor/drive required.

NOTES:
1. Motor drive ranges:

(E) Low Range: 687-873 rpm, 5.75 bhp
(F) Mid-Low Range: 805-1007 rpm, 5.75 bhp
(G) Mid-High Range: 941-1176 rpm, 8.63 bhp
(H) High Range: 1014-1297 rpm, 11.50 bhp
All other rpms require field-supplied motor or drive.

2. See below for general fan performance notes.

GENERAL NOTES FOR FAN PERFORMANCE DATA TABLES

1. Static pressure losses (i.e., economizer, electric heat, etc.) must be added

to external static pressure before entering Fan Performance table.

2. Interpolation is permissible. Do not extrapolate.
3. Fan performance is based on wet coils, clean filters, and casing losses.

See Accessory/FIOP Static Pressure information on page 39.

4. Extensive motor and drive testing on these units ensures that the full

horsepower range of the motor can be utilized with confidence. Using the
fan motors up to the bhp rating shown will not result in nuisance tripping or
premature motor failure. Unit warranty will not be affected.

5. Use of a field-supplied motor may affect wire size. Recalculate the unit

power supply MCA and MOCP if required. Contact the local Carrier repre-
sentative for details.

6. Use the following formula to calculate Input Watts:

Input Watts = Bhp x (746/motor eff.)

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

6,500

799

2.58

833

2.79

872

3.05

914

3.36

958

3.71

7,000

856

3.19

887

3.41

921

3.67

958

3.98

999

4.33

7,500

913

3.89

941

4.12

972

4.39

1006

4.69

1042

5.04

8,000

971

4.69

996

4.93

1024

5.20

1055

5.51

1088

5.86

8,500

1029

5.60

1052

5.85

1078

6.12

1106

6.44

1136

6.78

9,000

1087

6.62

1108

6.87

1132

7.16

1158

7.47

1185

7.82

9,500

1145

7.75

1165

8.02

1187

8.31

1211

8.63

1236

8.99

10,000

1203

9.01

1222

9.29

1243

9.59

1265

9.92

1288

10.28

10,500

1261

10.40

1279

10.69

1299

11.00

1319

11.34

1341

11.70

11,000

1320

11.93

1337

12.23

1355

12.55

1374

12.89

1394

13.26

11,500

1378

13.61

12,000

12,500

AIRFLOW

(Cfm)

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

Rpm

Bhp

6,500

1005

4.12

1052

4.57

1100

5.06

1148

5.60

1195

6.17

7,000

1041

4.72

1084

5.16

1128

5.64

1172

6.17

1217

6.74

7,500

1080

5.43

1119

5.86

1160

6.33

1201

6.84

1242

7.40

8,000

1122

6.24

1158

6.66

1195

7.13

1233

7.63

1272

8.17

8,500

1167

7.16

1200

7.58

1234

8.04

1269

8.53

1304

9.06

9,000

1214

8.21

1244

8.62

1275

9.07

1308

9.56

1340

10.08

9,500

1262

9.37

1290

9.78

1319

10.23

1349

10.71

1379

11.23

10,000

1312

10.66

1338

11.08

1365

11.52

1392

12.00

10,500

1363

12.09

1387

12.51

11,000

11,500

12,000

12,500

Bhp

Brake Horsepower Input to Fan

H

H

H

H

H

H

H

H

H

H

E

E

E

F

F

F

F

F

F

G

G

G

G

G

G

G

G

G

Advertising