Detex AO19-1 Push User Manual

Page 8

Advertising
background image

104850 Page 8

Low Voltage Activation Connections

You must disconnect all voltage sources before attempting to install an accessory.

Along with your Detex Low Energy Automatic Door Operator, you received an Installation Guide for

Detex Low Energy Operator Control Module, P/N 104827. This document will help with the proper

set up, switch options and wiring schematics.

The ON/OFF/HOLD 3-way toggle switch has been pre-wired into the Control Module and is located

at one end of the enclosure.

Before any adjustments can be made the following check must be performed. First the arm must

be properly connected to the door leaf. The power must be connected and the switch in the ON

position. The door leaf must be fully closed. Examine the Door Control. The control board must

have three lights illuminated (LATCH, POWER, and MODULE ON). If the CLOSE light is on, review

the arm assembly location by manually opening door leaf until it is stopped by internal stop. If the

door arm rotates well beyond 80 degrees refer back to arm installation directions. If arm stops at

approximately 80 degrees, allow the leaf to close.

The LATCH-CHECK AND BACK-CHECK are controlled via the cam on top of the gearbox. Access

is thru the top of the operator case directly above the gearbox. Using a 1/8th inch Allen wrench,

gently loosen the screw that holds the cam in place. Rotate cam in the closing rotation direction until

the CLOSE light goes out and the LATCH light comes on. Holding the cam in place gently retighten

the holding screw.

DO NOT OVER TIGHTEN AS THAT WILL DAMAGE THE CAM.

Test the LATCH-CHECK position by manually opening the door leaf until you see LATCH-CHECK

light go out and the CLOSE light comes on. This should be approximately 4 inches from Jamb. Fine

tune adjustment as necessary.

If the lights fail to work call for factory assistance.

THE DETEX, LOW ENERGY AUTOMATIC DOOR OPERATOR, IS TO BE USED WITH

APPROVED SWITCHES.

Contact factory for information on Sensor connections.

Typically you will use a wall mounted, hard wired push button for activation. You must provide wire

from the push button switch to the Control Module inputs. Knockouts are available on the enclosure

for wire runs. The connections are terminated on

terminals #1 and #2 of the Control Module.

Refer to the diagram included with the Control Module.

BE SURE ALL WIRING MEETS ALL STATE AND LOCAL CODES.