E

LECTRICAL

The tuner motor is connected to the control unit at the factory and supplied with a

length of conduit appropriate to the chamber. The control unit should be mounted

on the wall of the chamber within easy reach to operate the emergency switch.

Each tuner motor is a three-phase unit with a variable speed drive control. Each

motor uses less than eight amps under normal load.

The unit should be connected to a protected 208–230 volt, 15A supply, with the

wires connected as follows:

Brown:

Phase 1

Blue:

Phase 2

Green / Yellow:

Earth

For chambers with two tuners, the motor controllers can be connected to a single

20-amp supply.

V

ERTICAL

T

UNER

I

NSTALLATION

1.

Install the motor end of the tuner as described in the installation

procedures beginning on page 18.

2.

Using on the inner mounting plate, mount the idler bearing as

described in the installation procedures beginning on page 18.

3.

Fix the plate to the inner shield surface using adhesive or wood screws

penetrating only the inner surface of the panel.

Tuner Control – SMART 1000

The SMART™ (Statistical Mode Averaging Reverberation Test Site)

1000 chambers are fitted with a dedicated motor drive control unit mounted onto

the back of the chamber. This unit controls the motors for both the vertical and

horizontal tuners. The motors are linked to 10:1 gear box and use half-stepping,

providing 400 steps per revolution. The motor controller is set so that the

required angular position of the motor is defined by

θ/4.5, which means that the

angular position used in the seek command must be divided by 4.5.