Smart Power Systems HR-110 User Manual

Page 26

Advertising
background image

Smart Power

®

Systems

A. C. MODULAR GENERATOR SYSTEM

Page 25 of 53

WARNING:


Never operate the system without the filler/breather plug installed. Contaminants
may enter the hydraulic fluid through the filler opening, causing premature wear on
the hydraulic components and void the system’s warranty.

Never apply a load to the generator while there is air trapped in the hydraulic fluid.
Damage to the system’s hydraulic components, as well as ruptured hoses, may
result and void the system’s warranty.

Always run the purge cycle after installation, after replacing the hydraulic fluid and
the filter, or after making any other repairs that may allow air into the hydraulic
system. Failure to do so will void the system’s warranty.


Enabling System Purge Option

The purge option can also be set by performing the following steps:

Step 3: Hold Mode
until Amps Line 1
Blinks

. Release

switch so



appears.

Step 4: Press mode to
make

 appear.

Step 5: Press On/Off
until  appears.

Figure 13

1. If the Command & Control Center is dark, press the Mode switch to put

the display into Normal mode.

2. If the Display looks like Figure 13, The purge option is enabled.
3. Otherwise, press and hold the Mode switch until the Amps Line 1 field

begins blinking

 (more than 10 seconds). Release the switch so 

appears. Reference Figure 13.

4. Press (and release) the Mode switch until

 appears.

5. Press the On/Off switch until a

 appears, indicating Purge option is

Active.

6. Return to system purge display by pressing the Mode switch repeatedly

until the screen shown in Figure 13 is displayed. Purge will still be active.

Advertising
This manual is related to the following products: