A. C. MODULAR GENERATOR SYSTEM

Page 26 of 53

Indicates whether the
generator is

 or 

Example of display with purge option set

Figure 14

f. Engage the Power Take-Off (PTO). (Note: Pump may sound rough for a few

minutes due to entrapped air.) Make sure the Command & Control Center
displays the string “

” as shown in Figure 14, press the On/Off switch to turn

the generator off, if needed.

g. Check for hydraulic fluid leaks, all hose connections must be tight. Monitor the

hydraulic fluid level, adding fluid as needed to keep the level in the sight
gauge full
.

h. After 10 minutes, the system controller will automatically switch the generator to

”. Check to see that the generator is turning (The frequency display should

indicate

). If it is not, press the On/Off switch on the Command & Control

Center to start the generator.

i. After the generator has been operated for 20 minutes with the generator on, the

system controller will automatically disable the purge option.

Verify that the generator’s output frequency is 59-62 Hz. If the frequency is not
within that range, contact Smart Power Systems at (231) 832-5525 for more
information.



11.

Prior to applying full load, and after the oil temperature is above 100°F verify proper
operation of the cooler fan by feeling for airflow being pushed out of the tray
assembly. If the air is not being pushed through the cooler face contact Smart
Power

®

Systems at (231) 832-5525 for more information. Also verify that the air

passing through the cooler and the fan is not restricted.