DRAFT INDUCER CONNECTED WITH UP TO 4 24V GAS APPLIANCES WITH THE MAC-4 CONTROL

(MODEL HD REQUIRES USE OF MOTOR ISOLATION RELAY / CONTACTOR, SEE TOP OF PAGE 7)

GAS WIRING TO ANY APPLIANCE EQUIPPED WITH 24V CONTROLS

POST-PURGE RELAY/TIMER ON DRAFT INDUCER (DRAFT INDUCER MOTOR LESS THAN 4.4 AMPS)

MODELS I, IL, XL MUST USE 950-0483 ISOLATION RELAY

GAS WIRING TO ANY APPLIANCE WITH MILLIVOLT CONTROLS

REQUIRES POST-PURGE RELAY/TIMER ON DRAFT INDUCER (DRAFT INDUCER MOTOR LESS THAN 4.4 AMPS)

MODELS I, IL, XL MUST USE 950-0483 ISOLATION RELAY

COMPONENTS NEEDED:

(1) DRAFT INDUCER
(1) PS1505 FAN PROVER
(1) 950-1067 RELAY/TIMER

MAXIMUM AMP LOAD
IS 4.4 AMPS

COMPONENTS NEEDED:

(1) DRAFT INDUCER
(1) RELAY/TIMER

950-1067
MAXIMUM AMP LOAD
IS 4.4 AMPS

(1) WHK-I KIT
(1) 950-0470 THERMO-
COUPLE JUNCTION
ADAPTER (FOR
RESIDENTIAL WATER
HEATERS ONLY)

COMPONENTS NEEDED:

(1) MAC-4 APPLIANCE CONTROL
(1) DRAFT INDUCER
(1) PS1505 FAN PROVER

NOTE: The MAC-4 is used for
wiring up to 4 heating appliances
with Draft Inducers, Power Venters
or IN-FORCERs. It is suitable for
any combination of 24 VAC and 115
VAC control systems for gas and oil
burners.

IF DRAFT INDUCER MOTOR IS OVER 4.4
AMPS, WIRE 950-0483 ISOLATION RELAY
AS SHOWN IN THIS DIAGRAM.

IF DRAFT INDUCER MOTOR IS OVER 4.4
AMPS, WIRE 950-0483 ISOLATION RELAY
AS SHOWN IN THIS DIAGRAM.