DRAFT INDUCER CONNECTED WITH UP TO 4 24V GAS APPLIANCES WITH THE MAC-4 CONTROL

(DRAFT INDUCER MOTOR LOAD GREATER THAN 1 H.P.)

MULTIPLE DRAFT INDUCERS, POWER VENTERS OR IN-FORCERS CONNECTED WITH UP TO 4 24V GAS APPLIANCES

(IF INDIVIDUAL OR COMBINED MOTOR LOAD IS OVER 1 H.P. ISOLATION RELAY(S) WILL HAVE TO BE ADDED, SEE ABOVE)

COMPONENTS NEEDED:

(1) MAC-4 APPLIANCE CONTROL
(1) DRAFT INDUCER
(1) PS1505 FAN PROVER
(1) ISOLATION RELAY/CONTACTOR

NOTE: The MAC-4 is used for
wiring up to 4 heating appliances
with Draft Inducers, Power Venters
or IN-FORCERs. It is suitable for
any combination of 24 VAC and 115
VAC control systems for gas and oil
burners.

COMPONENTS NEEDED:

(1) MAC-4 APPLIANCE CONTROL

DRAFT INDUCER(S)
PS1505 FAN PROVER(S)
MOTOR ISOLATION RELAY /
CONTACTOR(S) IF OVER 1 H.P.

NOTE: The MAC-4 is used for
wiring up to 4 heating appliances
with Draft Inducers, Power Venters
or IN-FORCERs. It is suitable for
any combination of 24 VAC and 115
VAC control systems for gas and oil
burners. Wire Fan Prover(s) or
Limit(s) in Series with Prover termi-
nal block. Do not supply voltage to
Prover terminal block!