TROUBLESHOOTING ELECTRICAL PROBLEMS

16

The following guide is intended to be used if a problem occurs during
the use of the SS1-R side wall vent system. At several steps
throughout the guide you will be required to measure 115 Volts with
a voltmeter, (See Diagram T).

Extreme caution must be exercised to prevent injury. If you are
unable to determine the defective part with the use of this guide, call
your Tjernlund distributor or Tjernlund Products direct at 1-800-255-
4208 for further assistance.

Step 1.

Verify that 115V is present between "L1" and "L2"
on terminal strip, (See Diagram T).

Check circuit breaker or fuse

and electrical connections.

SS1-R and appliance are not interlocked correctly or

malfunction of appliance controls. Refer to

electrical diagrams in this manual and appliance
manufacturer's troubleshooting guide.

Replace Timer/Relay,
Part #950-1067.

Replace Motor, Part #950-0625.

No

No

No

Yes

Yes

Yes

SYMPTOM 1: SS1-R MOTOR WILL NOT OPERATE

Step 2.

With thermostat calling for heat, check for voltage
between "O" and "R" of terminal strip.

Step 3.

Verify that 115V is present between "M" and "L2"
on timer/Relay.

Remove the external control wire attached to terminal
"O" of the SS1-R terminal strip. This should cause the

motor to shut down within ten minutes (after the post-
purge cycle has finished).

SS1-R and appliance are not interlocked correctly.
Voltage is present at terminal "O" constantly. Voltage
should cycle on/off with appliance cycles. Refer to
electrical diagrams in this manual. Rewire according
to appropriate diagram.

Replace Timer/Relay,

Part #950-1067.

No

Yes

SYMPTOM 2: SS1-R MOTOR RUNS CONTINUOUSLY

DIAGRAM T