Tjernlund VP-2F, VP-3F Airotronics Timer 8504140 Rev A 11/11 User Manual

Page 13

Advertising
background image

12

Note: For further assistance contact

Step 3.2

Step 6

Step 3.1

Step 5

Solution

Step 4

Solution

Step 3

Step 2

Step 1

Symptom 2

at 1-800-255-4208, 7:30 - 4:30 CST.

Technical Customer Service Department

the Tjernlund Products, Inc.

Yes

Yes

Yes

No Blockage

No

No

Yes

No

Yes

Venter will not run.

Establish that all 115 volt circuits are

complete to the Power Venter. Check

the electrical plug to the wall receptacle,

circuit breakers, and fuses.

CAUTION: Disconnect the 115 volt

power supply to the Power Venter be-

fore attempting the following procedure.

a) Remove the two Black leads from

Remove the 1/4" tubing from the

Tjernlund Gas Pressure Switch and

check ends of the tubing for blockage

Check for gas pressure at the Pressure

Tap Port on the gas valve while the

burner is operating.

Consult with water heater manufacturer

for further assistance.

Re-establish 115 volts to the Power

Venter.

Replace the Power Venter motor.

Motor Part Number

VP-2F 950-2020

Measure the voltage on terminals 4

and 5 on the Relay/Timer.

Measure the voltage on the secondary

side of the 115/24 volt transformer.

the Relay/Timer and connect them

8079002 7-18-07

Solution

Part # 950-0014 non-adjustable,

Replace the Relay/Timer.

or Part # 950-1067 one to ten minute

No

VP-3F 950-1020

together.

supply to the Power Venter.

b) Re-establish the 115 volt power

Result: The Power Venter should run

constantly.

Result: At this time you should measure

approximately 24 volts.

No

Replace the 25' Control Cable from

the electrical box to the Gas Pressure

Yes

Switch.

Solution

Replace the Transformer.

No

Solution

Part # 950-2030

Result: At this time you should measure

approximately 24 volts.

Result: The Power Venter should run

the Gas Pressure Switch.

b) Jump the Red and Blue leads from

Step 2 to their original terminals.

a) Reinstall the two Black leads from

fore attempting the following procedure.

power supply to the Power Venter be-

CAUTION: Disconnect the 115 volt

constantly.

supply to the Power Venter.

c) Re-establish the 115 volt power

Repair or replace the 1/4" tubing as

necessary.

Solution

Replace the Tjernlund Gas Pressure

Yes,

Switch. Part # 950-2080

Solution

or kinks.

Result: Pressure is present.

Blockage

adjustable.

Note: For further assistance contact the Tjernlund

Products, Inc. Technical Customer Service
Department at 1-800-255-4208, 7:30 - 4:30 CST.

NOTE: If the pilot light is extinguished, follow the steps under “IN THE
EVENT OF A PILOT OUTAGE” on page 1 of these instructions before continuing.

Advertising