IN-FORCER MODELS PAI-10 & PAI-20 (0IL) TROUBLE SHOOTING GUIDE

Wiring not correct

No

Step 2.

When appliance is calling for heat measure for 115

volts across the Primary Control leads.
Result: 115 volts measured.

Step 1.
Recheck all wiring per the installation instructions.

Step 3.
Connect the BLACK, WHITE and GREEN wires in
the IN-FORCER directly to a constant 115 volt
power source.
Result: IN-FORCER runs constantly.

Wiring correct

Yes

Step 4.
Contact Tjernlund Products for further assistance.

Yes

Solution: Rewire the IN-FORCER per the
installation instructions or contact Tjernlund
Products for further assistance.

Solution: Contact appliance manufacturer
for further assistance.

No

Solution: Replace IN-FORCER motor.
Part # 950-3022

Note: For further assistance contact Tjernlund Products, Inc.
Technical Customer Service Department at 1-800-255-4208.

Wiring not correct

No

No

SYMPTOM 1: IN-FORCER PAI-O (OIL) SERIES RUNS BUT BURNER DOES NOT FIRE

SYMPTOM 2: IN-FORCER PAI-O (OIL) SERIES WILL NOT RUN ON CALL FOR HEAT

Step 2.

With the appliance calling for heat and IN-

FORCER running, measure for voltage across the
YELLOW of Fan Proving Switch and WHITE of
Cad Cell Relay.
Result: Measure 115V.

Step 1.
Recheck all wiring per the installation instructions.

Step 3.
Repeat step 1 & 2 or contact Tjernlund Products
for further assistance.

Wiring correct

Yes

Solution: Rewire the IN-FORCER per the
installation instructions or contact Tjernlund
Products for further assistance.

Solution: Replace
Fan Proving Switch.
Part # 950-0452.

Solution: Clean intake
screen of clogged mate-
rial. Check for exces-
sive length or sharp
bends in discharge or
inlet vent pipe.

Note: For further assistance contact Tjernlund Products, Inc.
Technical Customer Service Department at 1-800-255-4208.