IN-FORCER MODELS PAI-1G & PAI-2G (GAS) TROUBLE SHOOTING GUIDE

Wiring not correct

No

SYMPTOM 2: IN-FORCER PAI-G (GAS) SERIES RUNS CONSTANTLY

Step 2.
Remove the BLUE wire from the #7 terminal on
relay while IN-FORCER is running.
Result: IN-FORCER should shut off immediately.

Step 1.
Recheck all wiring per the installation instructions.

Step 3.
Measure for voltage on appliance thermostat or
aquastat when not calling for heat.
Result: Voltage not measured.

Yes

Yes

Step 4.
Contact appliance / thermostat manufacturer for
further assistance.

Yes voltage measured

Solution: Rewire the IN-FORCER per the
installation instructions or contact Tjernlund
Products for further assistance.

Solution: Replace the
IN-FORCER relay.
Part # 950-1040

No voltage measured

Solution: Repeat step 1-3 or contact
Tjernlund Products for further assistance.

Note: For further assistance contact Tjernlund Products, Inc.
Technical Customer Service Department at 1-800-255-4208.

Wiring not correct

SYMPTOM 1: IN-FORCER PAI-G (GAS) SERIES RUNS BUT BURNER WILL NOT FIRE

Step 2.

With the appliance calling for heat and the IN-

FORCER running, check for voltage across
YELLOW and RED control cable leads.
Result: Measure 24 volts.

Step 1.
Recheck all wiring per the installation instructions.

Step 3. (Wired with gas valve)

With the appliance calling for
heat and the IN-FORCER run-
ning, check for 24 volts across
the TH(HOT) and TR(COM) ter-
minals on appliance gas valve.
Result: Measure 24 volts.

Step 3. (Wired with single
zone gas or oil furnace
terminal strip/fan center)
With the thermostat calling for
heat and the IN-FORCER run-
ning, check for 24 volts across
the W and C(COM) terminals
on appliance terminal strip/fan
center.
Result: Measure 24 volts.

Step 4.
Contact appliance manufacturer for further assistance.

Yes

Solution: Rewire the IN-FORCER per the
installation instructions or contact Tjernlund
Products for further assistance.

No

obstructions

Solution:Replace
Fan Proving
Switch.
Part # 950-0452.

Solution: Clean intake
screen of clogged mate-
rial. Check for exces-
sive length or sharp
bends in discharge or
inlet vent pipe.

No

Solution: Repeat steps 1-3 or contact
Tjernlund Products for further assistance.

Note: For further assistance contact Tjernlund Products, Inc.
Technical Customer Service Department at 1-800-255-4208.