Tjernlund VSUB Series Universal Blowers for Combustion Air or Draft  8504114 User Manual

Page 14

Advertising
background image

4. Slowly turn VFD speed control knob counter-clockwise in 5 Hz increments every 5 minutes until a decrease in the draft in the

heater furthest from the chimney termination is measured or when any of the heaters starts to spill flue gases. Turn PSA-1 adjust-
ment screw clockwise in 1/4 turn steps waiting 30 seconds between each turn until the PSA-1 switch opens, causing the heaters to
be disrupted. Turn the PSA-1 adjustment screw 1/4 turn counter-clockwise and replace electrical box cover.

5. Note the frequency displayed Hz _____ (speed) on the VFD display and turn VFD speed control knob clockwise until 5 additional

Hz. is displayed Hz _____ (speed). Verify that all heater’s draft falls within the manufacturer’s recommended range. Increase
VSUB Blower speed if necessary to help achieve desired draft range.

SAFETY INTERLOCK TEST

1. Adjust the appliance thermostat(s) or aquastat(s) to call for heat.

2. Determine that the VSUB Blower operates before the gas valve or burner becomes energized.

3. With the appliance(s) and VSUB Blower operating, disrupt power to the VSUB Blower and determine that the appliance

gas valve(s) or burner motor(s) shut off.

Do not operate an appliance that does not shut off with the VSUB Blower disabled.

COMBUSTION AIR

Adequate combustion air is vital for proper combustion and for safe venting. Likewise, for proper inducer performance, adequate
combustion air must be available to the appliance. Many installers assume adequate combustion air is present, especially in older
structures. In some cases this is a false assumption because many structures have been made "tight" due to weatherization. Size
the combustion air opening(s) into the equipment room as outlined in NFPA 31, 54 & 211. Tjernlund’s IN-FORCER

TM

or Auto-Draft®

VSUB combustion air intake systems provide a convenient, automated way to supply combustion air to the equipment room. When
installing the VSUB Blower as a draft inducer, it is not necessary to supply any more combustion air than normally required when con-
ventional venting.

MAINTENANCE, SERVICE & HOUSING ROTATION

Disconnect the power supply when making wiring connections or when working around the fan impeller and motor. Failure
to do so can result in electrical shock, personal injury, death or property damage.

The Tjernlund VSUB Blower is designed for continuous use. The motor is equipped with permanently lubricated sealed ball bearings
which do not require regreasing.

A vent/duct pipe inspection must be performed annually. The inspection should include checking all vent/duct pipe and connections
for blockage and leaks. A safety interlock test must also be performed.

Inspect impeller after (3) months and set up a periodic inspection and cleaning routine as necessary.

Intake Hood and prefilters when Using VSUB as a combustion air intake:
Intake Hood screen, prefilters and blower impeller should be clear of any foreign material such as leaves, lint or other items.

SLIDE-OUT SERVICE & HOUSING ROTATION

The VSUB Blowers feature a slide out motor/blower impeller assembly for
easy servicing. The blower housing can be rotated 180° in 45° increments
so the discharge orientation best matches the job requirements. The
motor/blower impeller assembly must be completely slid out prior to rota-
tion of the housing.

TO SLIDE OUT MOTOR/BLOWER IMPELLER ASSEMBLY:

NOTE: Nuts on bottom can be removed through access openings.

Do not overtighten stainless steel fasteners.

1. Remove (8) nuts and washers from motor mount plate.

2. Remove (2) nuts and washers from the bottom stud of each side of

the motor mount flange.

3. Loosen nuts on motor mount base and slide motor/blower impeller

assembly out of housing.

13

ACCESS OPENING

MOTOR MOUNT BASE

MOTOR MOUNT FLANGE

SUPPORT BRACKET
(VSUB16 & 20 ONLY)

INLET

HOUSING
SUPPORT BRACKET

HOUSING STUDS

MOTOR MOUNT
PLATE STUDS

L

E

T

R O

T A T E

S

1

8

0

°

I

N

4

5

°

I

N

C

R

E

M

E

N

T

S

T

U

O

MOTOR

MOUNT

PLATE