Troubleshooting guide, Unit has ice forming on the evaporator, Unit does not run/power up – Vintage Cellars WhisperKOOL InCellar User Manual

Page 30: Cellar temperature is to warm, System runs constantly

Advertising
background image

InC

033114

Page 28 | 1-800-343-9463

TROUBLESHOOTING GUIDE

Unit has ice forming on the Evaporator

Possible Cause

Solution

Evaporator coil is dirty.

Clean coil with a vacuum.

If coil is very dirty, use a small hand spray with a small amount

of liquid dish washer detergent. Spray coil, let set for 5 min, then

flush with fresh water.

There is something blocking the supply and or return air

Remove blockage

The evaporator fan is not turning on.

Call a service tech to troubleshoot

The Unit has not gone through its anti-frost sequence, yet.

Check for ice in the depth of the coil. Melt with blow drier

until coil is warm to the touch. Soak up water with a towel.

If Unit continues to ice.

Observe ice formation pattern. If only part way up the coil

face, the system could be low on refrigerant. If all the way

up, the coil may be dirty or airflow is blocked.

Unit does not run/power up

Possible Cause

Solution

Unit is not plugged in

Make sure the unit is plugged into an outlet

Power switch not on

Turn unit on by pressing the power button on the control

Line voltage is incorrect rating for the system

Check line voltage to make sure there is 110v/120v

Bottle at set point

Lower set point

Thermostat not calling for cooling

Lower set point

Faulty thermostat or wiring

Call Customer Service at 1-800-343-9463

Cellar Temperature is to Warm

Possible Cause

Solution

The temperature of the room supplying the condenser

side of the unit has exceeded 110°F

Intake temperature needs to drop below 110°.

The unit is undersized for the cellar.

Order correct size system

There is something blocking the supply and/or return air,

on the Evaporator or the Condenser side of the Unit.

Remove air flow obstruction

One or more of the fans are not turning on.

Please contact the installing technician to troubleshoot.

Compressor is not turning on.

Please contact the installing technician to troubleshoot.

Compressor keeps cycling on overload

Make sure all fans are working and there are no airflow

obstructions.

Poor seal around door or other areas requiring a seal

(around the unit, wall joints, etc)

Make sure there are no air gaps around the door. If door

seal is damaged, replace it.

Controller Set Point set too high

Lower the set point.

Evaporator coil is frosted or iced up

Observe ice formation pattern. If only part way up the coil

face, Unit could be low on refrigerant. If so, contact your

installing technician to assist with troubleshooting.

System Runs Constantly

Possible Cause

Solution

Leaky door seal or poorly insulated cellar.

Fix leaky door seal and insulate cellar in accordance with

this manual. (Page 9)

Advertising