- 18 -

If the low ambient condition kit is used, turn off the compressor and
power the condensing unit (The compressor switch is located at the
outlet box of the condensing unit). Then turn on the compressor and
power the evaporator unit after the condensing unit has been powered
for 12 hours.

NOTE:
Make sure the fan speed control is turned on.

• Turn on the power.
• Press temperature controller

to turn on the unit.

• It is necessary to check the air flow to meet the specified CFM. It may use fan

speed control to adjust the system refrigeration performance to achieve 8-
10°F differential between return air and supply air while wine room
temperature is maintained 55°F. Turn the control knob clockwise to decrease
the air flow or counter-clockwise to increase the air flow.

Fig. 6 Fan Speed Control