Wine-Mate DS Series User Manual

Page 23

Advertising
background image

- 22 -

2. Connecting Electrical Wires

Connect all electrical components using the wiring diagrams in accordance with
all state and local codes.

4. Evacuating, Charging and Starting the system

CAUTION:
Always use the superheat and subcooling, pressure readings to charge

refrigerant properly; the listed charge amounts are used for reference
only.

If the unit is equipped with a low ambient condition kit and installed in

the summer, charge 15% more refrigerant.

If the low ambient condition kit is used, turn off the compressor before
power the condensing unit. Only turn on the compressor after the
condensing unit has been powered for 12 hours.


1) Evacuate the system; both discharge and suction valves must be in the

middle positions during evacuating.

2) Charge the system through both discharge and suction valves with refrigerant

using the recommended initial amount; both discharge and suction valves
must be in the middle positions during charging.

3) Connect the power to start the system and check the following temperatures

and pressures.


5. Adjusting and Completing the Installation

1) It may use a fan speed control to adjust the air flow to achieve the specified

CFM. The fan will run from the minimum speed to full speed with the control
knob at the lowest and highest speed position. To adjust the minimum speed,
turn control knob to the lowest speed position, then rotate the setting (located
on the side or front) clockwise to decrease the minimum speed or counter-
clockwise to increase the minimum speed. The minimum speed should be
adjusted until it supplies the required CFM.

2) The subcooling at the condensing unit shall be around 10°F. The charge may

be sufficient when there are no more bubbles forming in the liquid indicator.

3) Head pressure range: 120 ~ 150 psig at 70 ~ 90 °F condensing unit ambient

temperature.

4) The evaporator’s constant pressure expansion valve is set around 30 ~ 35

psig (35 ~ 40°F) at factory. This pressure setting gives a dew point to
maintain the proper humidity for storing wine.

5) The temperature split across the evaporator shall be 8 ~ 10°F at 55°F wine

cellar temperature.

6) Again, you must verify if the superheat at the evaporator unit is around 9 ~

18°F at 55 °F ~ high wine cellar temperatures.

Advertising