Wine-Mate DS Series User Manual

Page 24

Advertising
background image

- 23 -

7) If the superheat is high, check the subcooling first to know if the refrigerant

charge is sufficient. If the charge is not sufficient, add more refrigerant. If the
charge is good, then increase the evaporator suction pressure by turning the
hex nut (5/16”) clockwise. Liquid must always be charged into the hide side
when the compressor runs.

8) If the superheat is low, then decrease the evaporator suction pressure by

turning the hex nut (5/16”) counter-clockwise.

9) Both discharge and suction valves must be in the back positions before

disconnecting.

10) Close all service valves and disconnect all manifolds and hoses.

Fig. 11 Fan Speed Control Fig. 12 Expansion Valve

Fig. 13 Liquid Filter Fig. 14 Liquid Indicator

6. Pressure, Superheat and Subcooling Readings

CAUTION:
To read properly the service valves must be in the middle positions.

Complaint Possible

Causes

1) High suction pressure and low head pressure

Zero superheat and zero subcooling

2) High suction pressure and low head pressure

Low superheat and low subcooling

3) High suction pressure and high head pressure

Low superheat and high subcooling

1) Compressor may be bad

2) Expansion valve opened, too

much oil

3) Overcharge

Advertising