Block diagram/terminal configuration

Input

A1 A2

=

Power

=

K1

K2

13 23 33

51

24 34

52

14

43

44

*

Interface

base unit

63 73 83

74 84

64

93

94

*Safe separation in accordance with EN 60947-1, 6 kV

Function description

with PNOZsigma base unit:

}

Dual-channel operation via PNOZsigma connector

without PNOZsigma base unit:

}

Single-channel operation: one input circuit affects the output relays

Installation

Install contact expansion module without base unit:

}

Ensure that the plug terminator is inserted at the side of the unit.

Connect base unit and PNOZsigma contact expander module:

}

Remove the plug terminator at the side of the base unit and at the contact expander

module

}

Connect the base unit and the contact expansion module using the connector supplied,

before mounting the units to the DIN rail.

Control cabinet installation

}

The safety relay should be installed in a control cabinet with a protection type of at least

IP54.

}

Use the notch on the rear of the unit to attach it to a DIN rail (35 mm).

}

When installed vertically: Secure the unit by using a fixing element (e.g. retaining brack-

et or end angle).

}

Push the unit upwards or downwards before lifting it from the DIN rail.