Pilz PNOZ s11 C 24VDC 8 n/o 1 n/c User Manual

Page 9

Advertising
background image

PNOZ s11

Operating Manual PNOZ s11
21693-EN-08

9

Relay outputs

750111

751111

Utilisation category

In accordance with the standard

EN 60947-5-1

EN 60947-5-1

Auxiliary contacts, AC15 at

230 V

230 V

Max. current

5,0 A

5,0 A

Auxiliary contacts, DC13 (6 cy-

cles/min) at

24 V

24 V

Max. current

5,0 A

5,0 A

Safety contacts, AC15 at

230 V

230 V

Max. current

5,0 A

5,0 A

Safety contacts, DC13 (6 cycles/

min) at

24 V

24 V

Max. current

5,0 A

5,0 A

Contact fuse protection, external

safety contacts

In accordance with the standard

EN 60947-5-1

EN 60947-5-1

Blow-out fuse, quick

10 A

10 A

Blow-out fuse, slow

6 A

6 A

Circuit breaker, 24V AC/DC,

characteristic B/C

6 A

6 A

Contact fuse protection, external

auxiliary contacts

Blow-out fuse, quick

10 A

10 A

Blow-out fuse, slow

6 A

6 A

Circuit breaker, 24 V AC/DC,

characteristic B/C

6 A

6 A

Contact material

AgCuNi + 0,2 µm Au

AgCuNi + 0,2 µm Au

Conventional thermal current

while loading several contacts

750111

751111

Ith per contact at UB DC

Conv. therm. current with 1 con-

tact

6,00 A

6,00 A

Conv. therm. current with 2 con-

tacts

6,00 A

6,00 A

Conv. therm. current with 3 con-

tacts

6,00 A

6,00 A

Conv. therm. current with 4 con-

tacts

6,00 A

6,00 A

Conv. therm. current with 5 con-

tacts

6,00 A

6,00 A

Conv. therm. current with 6 con-

tacts

5,70 A

5,70 A

Conv. therm. current with 7 con-

tacts

5,30 A

5,30 A

Conv. therm. current with 8 con-

tacts

5,00 A

5,00 A

Advertising