A. shutdown with on/off/reset-off, Table 10a — shutdown with on/off/reset-off – Carrier 19XL User Manual

Page 283

Advertising
background image

Legend For Table 10, A - N

1CR AUX

—

Compressor Start Contact

OILPD

—

Oil Pressure

CA P

—

Compressor Current

OILT

—

Oil Sump Temperature

CDFL

—

Condenser Water Flow

PIC

—

Product Integrated Control

CHIL S S

—

Chiller Start/Stop

PRS TRIP

—

Pressure Trip Contact

CMPD

—

Discharge Temperature

PSIO

—

Processor Sensor Input/Output Module

CRP

—

Condenser Pressure

RLA

—

Rated Load Amps

ERT

—

Evaporator Refrigerant Temperature

RUN AUX

—

Compressor Run Contact

EVFL

—

Chilled Water Flow

SPR PL

—

Spare Protective Limit Input

GV TRG

—

Target Guide Vane Position

SMM

—

Starter Management Module

LID

—

Local Interface Device

STR FLT

—

Starter Fault

MTRB

—

Bearing Temperature

TXV

—

Thermostatic Expansion Valve

MTRW

—

Motor Winding Temperature

V P

—

Line Voltage: Percent

V REF

—

Voltage Reference

Table 10A — Shutdown with On/Off/Reset-Off

Primary Message

Secondary Message

Probable Cause/Remedy

Manually Stopped —
Press

CCN or Local to Start

PIC in OFF mode, press the CCN or
local softkey to start unit.

Terminate Pumpdown
Mode

To Select CCN or Local

Enter the Control Test table and
select Terminate Lockout to unlock
compressor.

Shutdown In Progress

Compressor Unloading

Machine unloading before shutdown
due to Soft Stop feature.

Shutdown In Progress

Compressor Deenergized

Machine compressor is being com-
manded to stop. Water pumps are
deenergized within one minute.

Ice Build

Operation Complete

Machine shutdown from Ice Build
operation.