Carrier 19XL User Manual

Page 388

Advertising
background image

19XL PIC SERVICE1 TABLE CONFIGURATION SHEET

DESCRIPTION

RANGE

UNITS

DEFAULT

VALUE

Motor Rated Load Amps

1 to 9999

AMPS

200

Motor Rated Line Voltage

1 to 9999

VOLTS

460

Meter Rated Line kW

1 to 9999

kW

600

Line Frequency
0=60 Hz/1=50 Hz

0/1

0

Compressor Starter Type

REDUCE/FULL

REDUCE

Condenser Freeze Point

–20 to 35
(–28.9 to 1.7)

DEG F
(DEG C)

34

(1.1)

Soft Stop Amps Threshold

40 to 100

%

100

CL-8

Advertising