SYSTEM ERROR TABLE
LED indication
Cause
Trouble points
SYS DATA RX
No data sync
Duplicated data sync
• Data Clock Switch on all units are set to
RCV position,
# Broken system data line with ’’RCV"
WJ-PCIO.
• Duplicated "SND" position of WJ-PCiO with
other units.
SYS DATA TX
Wrong Controller Unit No,
• Controller Unit No. is set either 0, 6, 7, 8 or
9 in PC-mode.
• Controller Unit No. is set other than 0 in
Extension-mode.
Duplicated Controller Unit No.
• Controller Unit No, duplicated with
WJ-PCiO in PC-mode.
RS-232 RX
75i7 termination error
• Broken or non-termination of system data
line with"SND" WJ-PCiO.
RS-232 TX
WJ-MP404 site error in PC-mode
• Duplicated "SND’' position of WJ-PCiO with
WJ-MP404.
• Duplicated "Unit No." of system components.
• Broken or non-termination of system data
line.