P30L User Manual

Revision 1.0


to adjust the parameter. After the value has been set, press the ‘MODE’ button for over 5 seconds to exit the
adjustable mode and store the setting.

3.4.9

Over Voltage Disconnect Interface

The value displayed in this interface is the value at which the charge controller will stop charging the battery.
When the battery voltage reaches this voltage, the controller will disconnect the charging solar panel(s) to
prevent the battery from overcharging. After the battery voltage drops below the Over Voltage Disconnect
value, the controller will reconnect the charging solar panel(s).

NOTE: To change the OVD value, press the ‘MODE’ button for over 5 seconds until the number starts to
blink / flicker. The controller will enter the adjustable mode, where you can use the ‘UP’ and ‘DOWN’ buttons
to adjust the parameter. After the value has been set, press the ‘MODE’ button for over 5 seconds to exit the
adjustable mode and store the setting.

3.4.10

Load Mode – Timed Control Interface

The P30L charge controller has a mode setting function to set specific operation parameters. It is preset to
the factory default of normal control (24 hours). In ‘Normal’ mode, the load will draw from the battery at all
times, and the PV panel will charge the battery when sunlight is available. It is also possible to have the load
remain on for a set duration, and when that set time period has elapsed, the load will switch off. The duration
setting is available in increments of 1 hour and 1-23 hour delays can be selected.

NOTE: To change the Load Control value, press the ‘MODE’ button for over 5 seconds until the number
starts to blink / flicker. The controller will enter the adjustable mode, where you can use the ‘UP’ and ‘DOWN’
buttons to adjust the parameter. After the value has been set, press the ‘MODE’ button for over 5 seconds to
exit the adjustable mode and store the setting.

Value

Mode

Function

24h

Normal (Default) Load is supplied continuous power.

1h – 23h

Timed Control

Load is supplied power at nighttime and continues working
for the specified duration (in hours). For example, if the Load
Control Value is set to 2h, then the load will be turned on at
night time and remain on for a period of 2 hours.

0h

Light Control

Load starts to supply power after dark and stops at dawn
(sunrise).

IMPORTANT: There is a 10 minute delay before turning on the load in order to make sure it is really dark
and not a passing cloud etc.

OVD Set Value

Load Mode Set Value

Page 12 of 16

windy

nation

01/20/2014