Table 1 – Physical Data -- Unit 50VT--A

50VT-A24

50VT-A30

50VT-A36

50VT-A42

50VT-A48

50VT-A60

Unit Size

2

2.5

3

3.5

4

5

Shipping Weight (lb)

(kg)

354

161

346

157

426

193

472

214

460

209

506

230

Compressor Quantity

1

Type

Scroll

Refrigerant

R-410A

Refrigerant Quantity (lb)

Quantity (kg)

11.1

5.0

10.3

4.7

9.9

4.5

11.3

5.1

12.5

5.7

15.2

6.9

Refrigerant Metering Device

Indoor TXV, Outdoor Dual Accuraters

Orifice OD (in)

(mm)

0.032 (2)

0.81 (2)

0.037 (2)

0.94 (2)

0.038 (2)

0.97 (2)

0.040 (2)

1.02 (2)

0.040 (2)

1.02 (2)

0.049 (2)

1.24 (2)

Outdoor Coil

Rows...Fins/in,

face area (sq. ft.)

2...21

13.6

2...21

13.6

2...21

13.6

2...21

17.5

2...21

17.5

2...21

23.3

Outdoor Fan

Nominal Airflow (cfm)

Diameter (in.)

Diameter (mm)

Motor hp (rpm)

2500

24

610

1/10 (810)

2700

24

610

1/5 (810)

3100

26

660

1/5 (810)

3100

26

660

1/5 (810)

3100

26

660

1/5 (810)

3500

26

660

1/4 (810)

Indoor Coil

Rows...Fins/in,

face area (sq. ft.)

3...17

3.7

3...17

3.7

3...17

4.7

3...17

4.7

3...17

5.6

3...17

5.6

Indoor Blower

Nominal Airflow (cfm)

Size (in.)

Size (mm)

Motor hp (rpm)

800

10 x 10

254 x 254

1/2

1000

10 x 10

254 x 254

1/2

1200

11 x 10

279 x 254

3/4

1400

11 x 10

279 x 254

3/4

1600

11 x 10

279 x 254

1

1750

11 x 10

279 x 254

1

High Pressure Switch (psig)

Cutout

Reset (Auto)

650 +/- 15

420 +/- 25

Loss-of-Charge/Low Pressure Switch (psig)

Cutout

Reset (Auto)

20 +/- 5

45 +/- 10

Return Air Filters

disposable (in)

(mm)

20x20x1

508x508x25

20x24x1

508x610x25

24x30x1

610x762x25

24x36x1

610x914x25

*Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating airflow

velocity of 300 ft/minute for throwaway type or 450 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN.

W.C.
{

If using accessory filter rack refer to the filter rack installation instructions for correct filter size and quantity.

}

For 460 volt units, add 14 lb (6.4 kg) to the weight.

Table 2 – Minimum Airflow for Reliable Electric Heater Operation (CFM)

SIZE

50VT--A24

50VT--A30

50VT--A36

50VT--A42

50VT--A48

50VT--A60

AIRFLOW (CFM)

800

1025

1250

1400

1710

1800

INDOOR
THERMOSTAT

DISCONNECT
PER NEC

FROM
POWER
SOURCE

RETURN
AIR

TOP COVER

POWER ENTRY

CONTROL ENTRY

A09098

Fig. 11 -- Typical Installation