Caution, Warning – Carrier PERFORMANCE 50VT-A User Manual

Page 19

Advertising
background image

19

4. Remove the vinyl cap off of the desired speed tap wire

(Refer to Table 3 for color coding) for the normal cooling

fan speed and place desired speed tap wire on “HIGH” on
the interface board.

5. Refer to airflow tables (Table 4) to determine allowable

speeds for the dehumidification cooling fan speed. In Table
4, speeds that are not allowed for dehumidification cooling

are shaded.

6. Remove the vinyl cap off of the desired speed tap wire

(Refer to Table 3 for color coding) for the dehumidification

cooling fan speed and place desired speed tap wire on the
“LOW” connection on the interface board (IFB). Verify

that static pressure is in the acceptable range for the speed
tap to be used for dehumidification cooling.

7. Use any spare vinyl plugs to cap any unused speed tap

wires.

Single Speed Cooling With Higher Electric Heat Speed

This unit can also be configured to operate with single speed
cooling and a higher speed for an accessory electric heater.

1. Move the two pin DEHUM jumper located on control

board (see Fig. 16) from the “STD” position to the

“DEHUM” position.

2. See Table 2 for minimum airflow for electric heat operation.

Add electric heater and filter pressure drop to duct system

static pressure to determine total external static pressure.

3. Select speed tap from Table 4 that will achieve required

airflow from Table 2.

4. Remove the vinyl cap off of the desired speed tap wire

(Refer to Table 3 for color coding).

5. Connect the desired speed tap wire to the “HIGH” terminal

on the interface fan board (IFB).

UNIT OPERATION HAZARD

Failure to follow this caution may result in unit component

damage or improper operation.
To use this mode, a speed connection must be made on the

“HIGH” terminal that meets or exceeds the minimum

airflow found in Table 2.

!

CAUTION

Table 3 – Color Coding for Indoor Fan Motor Leads

Black = High Speed

Orange = Med--High Speed

Red = Med Speed

Pink = Med--Low Speed

Blue = Low Speed

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Disconnect electrical power to the unit and install lockout

tag before changing blower speed.

!

WARNING

Continuous Fan Operation

When the DEHUM feature is not used, the continuous fan speed

will be the same as cooling fan speed. When the DEHUM feature
is used, the continuous fan will operate on IFB “LOW” speed

when the DH control lead is not energized, or IFB “HIGH” speed
when the DH lead is energized (see Fig. 16).

COMPRESSOR

ACCUMULATOR

OUTDOOR COIL

INDOOR COIL

LCS

LEGEND

HPS – High Pressure Switch

LCS – Loss of Charge Switch

Accurater

®

Metering De vice

Arrow indicates direction of flo

w

TXV in Metering

Position

Bypass

Position

HP S

C03011

Fig. 15 -- Typical Heat Pump Operation, Cooling Mode

50V

T

--

A